Digital Sensor

Installation

1. Open casing to remove back cover by pushing on the tab located
underneath the thermostat. (See Figure 1)
2. Pull wire(s) throught central hole of back cover.
3. Screw in the back cover to the wall.
4. Connect wires:
• If using twisted pair wires:
- Pull out screw terminal block.
- Remove 1 cm insulation from each wire.
- Connect the wires to the terminal blocks and reconnect
the terminal blocks. (See Figure 2)
• If using CAT5 cable:
- Plug the cable into the RJ45 jack of the T1000 (if CAT5 cable
is opened at the controller, refer to Figure 3 for pinout of the
T1000's RJ45 jack).
5. Reconnect top cover.
IMPORTANT! Do not install the thermostat under the following
conditions:
• Any location exposed to direct sunlight.
• On an outside wall.
• Near an air dischatge grill.
• In a location where vertical sir circulation is retricted.
• Near a dimmer switch.
10
(PL-T1000)
REV 1.0 / PL-QCK-WSENSOR/VC2000-EN