1.5 Arc Status

The Arc Status screen provides status information on each of the of the 16 Sensor inputs.
State
The State column determines the state of each sensor input. The following states are reported :
Disabled
Armed
ARC Sensor is armed
Tripped
ARC detected (changes for the period of the trip) Failed
ARC sensor supervision failure
Initializing
ARC sensor initializing (transitory) Stuck
ARC sensor stuck on
Flag
The Flag column will indicate and latch for an Arc Sensor operation, individual Flags may be reset by
clicking on the sensor flag status and entering the user name and password if prompted.
Count
The Count field provides a log of ARC sensor operations since power on or the last counter reset, the
individual sensor counters may be reset to 0 by clicking on the count field and entering the user name and
password if prompted.

1.6 Summary of RA24 SARC Configuration

The following steps outline the RA24 SARC Configuration :
Establish a Web Browser session using the default IP address
Set up the IP addressing for the SNTP server
Arm the ARC Sensor inputs to be utilized in the application
Set which outputs are to be operated by the respective ARC sensors
©2014 Siemens Protection Devices Limited
Figure 6: RA24 Arc Status
ARC Sensor is disabled
Chapter 2 Page 10 of 42