Section 4: 7SR22 Configuration

4.1 Logic Configuration

Our application is to employ a current check using the pickup of an Instantaneous Overcurrent Element (50-
1) to qualify an Arc Sensor operation. The following sections outline the logic implemented.

4.2 User output Allocation

Using the previously defined ARC Fault Sensor Zones we will nominate the User Outputs that will capture
the resultant SARC operation and current check logic.
Zone Coverage
Feeder Exit
Termination Chamber
Feeder CB Chamber
Bus
Incomer CB Chamber
Incomer Termination
Chamber
©2014 Siemens Protection Devices Limited
Colour
SARC Allocation
SARC 1
SARC 2
SARC 3
SARC 4
SARC 5
SARC 6

Table 5: RA24 User Output Allocation

Chapter 2) 7XG3124 Application Guide
User Output
User Output 1
User Output 2
User Output 2
User Output 3
User Output 3
Chapter 2 Page 35 of 42