REVO TC
USER'S MANUAL
TU-RS485-PNT0TCMxx
Rev. 09/2018
Serial Communication
Manual
PROFINET
00003

Advertisement

Table of Contents
loading

Summary of Contents for CD Automation REVO TC

  • Page 1 REVO TC USER’S MANUAL TU-RS485-PNT0TCMxx Rev. 09/2018 Serial Communication Manual PROFINET 00003...
  • Page 2: Table Of Contents

    Connection PN104 / PN108 ............................2 1.1.1.2 Status Led .................................. 2 1.1.1.3 Digital Output ................................3 1.1.1.4 Connection with Revo TC ............................4 1.1.1.5 Revo TC Addressing ..............................4 1.1.2 PLC C ................................. 5 ONFIGURATION 2 Data Exchange Area ...................... 7 2.1 Read area (E area)
  • Page 3: Fieldbus Communication

    REVO-TC / TU-RS485-PNT0TCMxx Communication Manual 1 FIELDBUS communication 1.1 PROFINET The thyristor unit have a data exchange via PROFINET Siemens protocol. 1.1.1.1 Connection PN104 / PN108 +24Vdc Not used Not used DO1 + DO1 - Master RS485 Master RS485 Tx/Rx+ Tx/Rx- Slave 1 RS485 Slave 1 RS485...
  • Page 4: Digital Output

    REVO-TC / TU-RS485-PNT0TCMxx Communication Manual 1.1.1.3 Digital Output The digital output, is an open collector output, used to indicate the communication error status. This option is available from firm Ver 2.24.000 and configuration Ver 1.2 Voltage supply :24Vdc Max current :150mAM Output Status...
  • Page 5: Connection With Revo Tc

    Master RS485 Tx/Rx- 1.1.1.5 Revo TC Addressing The Revo TC addressing on a Revo TC system is like follow Addr 1 Addr 2 Addr 3 Addr n The first Revo TC is address 1 the second address 2 and so on...
  • Page 6: Plc Configuration

    REVO-TC / TU-RS485-PNT0TCMxx Communication Manual 1.1.2 PLC Configuration With PROFINET connection is possible read value in cyclic mode. To do it you need use de GSDML plc configuration file that describe the product, and install in PLC configuration software environment. If GSD file is not installed, please install it If installed or after installation will be present (NIC 52-RE/PNS) The GSDML file is named “GSDML-V2.32-HILSCHER-NIC 5X-RE PNS-20161102.xml”...
  • Page 7 REVO-TC / TU-RS485-PNT0TCMxx Communication Manual Set output and Input with drag and drop NOTE: The module must have the right sequence Is important the position, and the: • Position 5 must be 64 Bytes Out • Position 6 must be 64 Bytes Out •...
  • Page 8: Data Exchange Area

    REVO-TC / TU-RS485-PNT0TCMxx Communication Manual 2 Data Exchange Area 2.1 Read area (E area) Columns The number of bytes from the “0” address to the parameter start Byte Bus Offset: address Word Bus Offset: The number of “Words” offset from the “0” address. Parameter The Modbus parameter number Number:...
  • Page 9 REVO-TC / TU-RS485-PNT0TCMxx Communication Manual PROFIBUS PROFINET Description Acyclic – Transmission Number 65635 Acyclic – Error Code Acyclic –Function code executed 3 or 6 Acyclic – Readed or Writed value 65635 Internal use ID 1 - PV ° Inp Low Inp High ID 1 - SP °...
  • Page 10 REVO-TC / TU-RS485-PNT0TCMxx Communication Manual PROFIBUS PROFINET Description 1000 ID 4 - PW H (0,0) (100,0) 1000 ID 4 - PW C (0,0) (100,0) ID 4 - Current CT Size (0,0) (xxx,x) ID 4 - Status ID 4 - Free ID 5 - PV °...
  • Page 11 REVO-TC / TU-RS485-PNT0TCMxx Communication Manual PROFIBUS PROFINET Description ID 7 - PW H 1000 (0,0) (100,0) ID 7 - PW C 1000 (0,0) (100,0) ID 7 - Current CT Size (0,0) (xxx,x) ID 7 - Status ID 7 - Free ID 8 - PV °...
  • Page 12 REVO-TC / TU-RS485-PNT0TCMxx Communication Manual PROFIBUS PROFINET Description ID 11 - SP ° SP Low SP High 1000 ID 11 - PW H (0,0) (100,0) 1000 ID 11 - PW C (0,0) (100,0) CT Size ID 11 - Current (0,0) (xxx,x) ID 11 - Status ID 11 - Free...
  • Page 13: Status Table

    REVO-TC / TU-RS485-PNT0TCMxx Communication Manual PROFIBUS PROFINET Description 2.1.1 Status Table Meaning Pretune Active Not Active Self Tune Active Not Active Auto/Manual Manual Auto On/Off sts out1 sts out2 sts out3 sts out4 Alm1 Active Not Active Alm2 Active Not Active Alm3 Active Not Active...
  • Page 14: Write Area (A Area)

    REVO-TC / TU-RS485-PNT0TCMxx Communication Manual 2.2 Write area (A area) PROFIBUS PROFINET Description 65635 Transmission number Not used Address to query (Fixed 1) Function to use 3 or 6 3 for read a value 6 for write a value 65635 Parameter number to read or write 65635 If function 6 is the value to write...
  • Page 15 REVO-TC / TU-RS485-PNT0TCMxx Communication Manual PROFIBUS PROFINET Description ID4 – Command Meaning On/Off Pretune Not active Active Auto/Manual Manual Auto ID5 - SP ID5 - P003 Pw ID5 – Command Meaning On/Off Pretune Not active Active Auto/Manual Manual Auto ID6 - SP ID6 - P003 Pw ID6 –...
  • Page 16 REVO-TC / TU-RS485-PNT0TCMxx Communication Manual PROFIBUS PROFINET Description ID9 – Command Meaning On/Off Pretune Not active Active Auto/Manual Manual Auto ID10 - SP ID10 - P003 Pw ID10 – Command Meaning On/Off Pretune Not active Active Auto/Manual Manual Auto ID11 - SP ID11 - P003 Pw ID11 –...
  • Page 17 REVO-TC / TU-RS485-PNT0TCMxx Communication Manual PROFIBUS PROFINET Description...
  • Page 18 REVO-TC / TU-RS485-PNT0TCMxx Communication Manual PROFIBUS PROFINET Description 200 100 202 101 204 102 206 103 208 104 210 105 212 106 214 107 218 109 220 110 222 111...
  • Page 19 REVO-TC / TU-RS485-PNT0TCMxx Communication Manual PROFIBUS PROFINET Description 224 112...
  • Page 20: Indirect Actions Function

    REVO-TC / TU-RS485-PNT0TCMxx Communication Manual 3 Indirect Actions function This function is used to read or write a value that is not in programmed in read or write area. This function are placed in write area from offset byte 0 to offset byte 10 PROFIBUS PROFINET Description...
  • Page 21: How Write A Value

    REVO-TC / TU-RS485-PNT0TCMxx Communication Manual 3.1 How Write a value To write a value need 1) Set Byte offset 2 fixed to 0 2) Set Byte offset 4 (Address) fixed to 1 3) Set Byte offset 6 (Function) to value 6 4) Set Byte offset 8 (Par Number) number of parameters in column “Parameter Number”...
  • Page 22: Who To Set Right Configuration

    REVO-TC / TU-RS485-PNT0TCMxx Communication Manual 4 Who to set right configuration The field bus module can be order configurated with right number of zone or empty To set the right zone number is enough connect the usb cable to a PC and copy the right configuration file.