5. Nominal Size Selection Method

5.1 Pressure reducing valve specification selection chart

5.2 Safety valve setting pressure

Reduced pressures (MPa)
0.03~0.1
0.1~0.4
0.4~0.6
0.6~0.8
0.8~1.4

5.3 Characteristics chart

(1) Flow rate characteristics chart
Shut-off pressure raise
Setting
pressure
0
5
Min.adjustable flow rate
(2) Pressure characteristics chart
Safety valve setting pressure (MPa)
Reduced pressures+more than 0.05
Reduced pressures+more than 0.08
Reduced pressures+more than 0.1
Reduced pressures+more than 0.12
Reduced pressures+15%
50
100
(%)
Flow rate
Rated flow
Find the intersection point of the inlet
and reduced pressures. The GP-1000
series valves are suitable within range
(A), (B), (C), and (D).
・Range(A) : GP-1000H
・Range(B) : GP-1000H、
・Range(C) : GP-1000H、
・Range(D) : GP-1002(1012)
• Shut-off pressure raise : 0.02 MPa or less
• Offset : 0.03 MPa or less
Offset
(Setting pressure: 0.03~0.1 MPa)
: 0.05 MPa or less
(Setting pressure: 0.1~1.4 MPa)
Reduced pressure is set to 0.1 MPa
when inlet pressure is 1.0 MPa. The
chart indicates a variation in reduced
pressure when the inlet pressure is
changed from 1.6 to 0.3 MPa.
-4-
GP-1000(1010)
GP-1000(1010)、
GP-1002(1012)
■EPDT-081a■