Window Master MotorController WCC 310 Installation Instructions Manual page 10

Standard versions
Table of Contents

Advertisement

When using actuators with MotorLink
cable cross
section [a]
Total
actuator current [I]
1A
2A
3A
4A
5A
6A
7A
8A
9A
10A
20A
®
the max cable length is 50m regardless of the result of the above mentions formula.
Actuators with MotorLink
Do not use the PE wire / green/yellow wire!
3 wire
3 wire
0,75mm²
1,50 mm²
42m
21m
40m
14m
28m
11m
21m
8m
17m
7m
14m
6m
12m
5m
11m
9m
8m
4m
®
5 wire
3 wire
1,50 mm²
2,50
2 wire
mm²
parallel
50m
47m
42m
35m
34m
28m
28m
23m
24m
20m
21m
18m
18m
15m
16m
14m
8m
7m
5 wire
3 wire
2,50 mm²
4,00 mm²
2 wire
parallel
50m
50m
50m
50m
45m
47m
37m
40m
32m
35m
28m
31m
25m
28m
22m
14m
11m
10