Items
CC-Link IE Field
Station type
Network Basic
Maximum number of connectable stations
Number of stations occupied by a slave station
Maximum number of link points per network
Maximum number of link points per
station
UDP port number used in the cyclic transmission
UDP port number used in the automatic detection of connected
device
Transmission
specifications
Network topology
*3
Hub
Connection cable
General-purpose
Transmission
Ethernet
specifications
communication
Protocol type
Number of connections
*3
Hub
Connection cable
Number of ports
Number of occupied I/O points
Applicable CPU module
Applicable engineering tool
Number of connectable units
2 SPECIFICATIONS
16
2.3 Performance Specifications
*1
Master
station
Slave
*2
station
Data transmission speed
Interface
Maximum station-to-station distance
Overall cable distance
Number of cascade
100BASE-TX
connections
*5
100BASE-TX
Data transfer speed
Communication mode
Transmission method
Interface
Maximum segment length (Maximum distance
between hub and node)
Number of cascade
100BASE-TX
connections
10BASE-T
*5
100BASE-TX
10BASE-T
Specifications
Master station
32
1 to 4
RX
2048
RY
2048
RWr
1024
RWw
1024
RX
2048
RY
2048
RWr
1024
RWw
1024
RX
64/128/192/256
RY
64/128/192/256
RWr
32/64/96/128
RWw
32/64/96/128
61450
Master station: An unused port number is assigned automatically.
Slave station: 61451
100 Mbps
RJ45 connector
100 m
Depends on the system configuration
For the number of the connectable stages when using a switching hub,
check with the manufacturer of the switching hub used.
Star topology
Hubs with 100BASE-TX ports
Ethernet cable of category 5 or higher (STP cable)
100/10 Mbps
Full-duplex or half-duplex
Base band
RJ45 connector
*6
100 m
*7
2 levels maximum
*7
4 levels maximum
Socket communication
Total of 32 connections
(Up to 32 external devices can access one FX5-ENET module at the
same time.)
Hubs with 100BASE-TX or 10BASE-T ports
Ethernet cable of category 5 or higher (STP cable)
Ethernet cable of category 3 or higher (STP/UTP cable)
*9
2
8 points
• FX5U CPU module (Ver. 1.110 or later)
*10
• FX5UC CPU module
GX Works3 (Ver. 1.050C or later)
1 module
*4
can be used.
*3
*8
can be used.
(Ver. 1.110 or later)

Advertisement

Table of Contents
loading

Table of Contents