Follow the operating procedure below to use the automatic detection of connected device.
1.
Start up a new project in GX Works3 and execute the automatic detection of connected device.
2.
Detected slave stations are reflected in the network configuration setting. Change the items such as the connection order
and numbers of occupied stations and set station numbers.
3.
Configure IP addresses and subnet masks of slave stations in the network configuration setting. And then, reflect the
settings to the slave stations.
Select a module on the list of stations or the network map  [Online]  [Communication Setting Reflection of Slave
Station]
4.
Parameters that are inherent in the slave stations can be read/written from/to the network configuration setting.
details on the parameters inherent in each slave station, refer to the manuals of the slave station used.
Select a module on the list of stations or the network map  [Online]  [Parameters Processing of Slave Station]
*1 To read parameters, select "Parameter read" from "Method selection" and click the [Execute] button. Parameters read are displayed in
the column of "Read Value". To write parameters, select "Parameter write" from "Method selection", input data to the column of "Write
Value", and then click the [Execute] button.
Slave station settings in the network configuration setting must be configured after executing the automatic
detection of connected device.
If not, contents of setting items that have been already configured in the network configuration setting are
overwritten by ones detected by the automatic detection. Detected slave stations are reflected in the network
configuration setting in ascending order of MAC address and values such as the number of occupied stations
becomes initial value.
If an error occurs while the automatic detection of connected device is being executed, the window shown below appears.
Each of the error codes listed below fills the last four digits of <0x2c09****>.
Error code
Error details and cause
C055H and C056H
System error
C059H
The function which is not supported by the target device
was executed.
C05CH
• The setting value of the communication setting is out of
range.
• Items of communication setting which cannot be set on
the target device are set.
• The required setting items have not been set to the
target device.
7 PARAMETER SETTINGS
34
7.3 Basic Setting
Action
• Check the precautions for the function executed.
• Check the operating status and connection status of the target device.
• Check the connection of the Ethernet cable and the hub.
• Check the line status of Ethernet.
• Reset the CPU module and target device, and execute the function again.
If the above actions do not solve the problem, contact the manufacturer of
the target device.
Check whether the function executed is supported by the target device.
Correct the setting details, and retry the operation.