Siemens SITRANS LR250 Operating Instructions Manual page 86

Radar transmitters
Hide thumbs Also See for SITRANS LR250:
Table of Contents

Advertisement

Remote operation
7.1 Operating via AMS Device Manager
Quick Start Wizard steps
Note
• Complete the steps in order. Click on Apply after revising parameters in each step, or
CANCEL to exit step without saving changes. (Note: Apply will write changes to the
device. OK will write changes to the device and exit to the Device Connection View.
CANCEL will exit to the Device Connection View without applying changes.)
• Do not use the Quick Start Wizard to modify individual parameters: see instead Changing
parameter settings using AMS Device Manager (Page 91). (Perform customization only
after the Quick Start has been completed.)
• Values set using the Quick Start Wizard via AMS Device Manager are saved and recalled
each time it is initiated (unlike the Quick Start Wizard initiated via the handheld
programmer).
• To run the Quick Start Wizard for this device, the RESOURCE block must first be set to
Out of Service (OOS) mode, before any configuration changes (changes to parameters
affecting block output) can be written. (Setting RESOURCE block to OOS also sets LTB
to OOS.)
• After completing steps 1-4, review all settings in Step 5 - Summary. Return to steps1-4 if
further changes are required.
• After completing the Quick Start Wizard from AMS, you must manually place the
RESOURCE block in Automatic mode.
Launch AMS Device Manager and double-click the device icon from the Device Connection
View to open the startup screen. Navigate to Configure/Setup > Resource Block > Wizards >
Quick Start, and click on Step 1 - Identification.
86
SITRANS LR250 (FOUNDATION FIELDBUS)
Operating Instructions, 08/2014, A5E32221411-AC