Siemens SITRANS LR250 Operating Instructions Manual page 75

Radar transmitters
Hide thumbs Also See for SITRANS LR250:
Table of Contents

Advertisement

Parameter type
Quick Start
Wizard
parameters
Independent
parameters
Return to Measurement: press Mode
SITRANS LR250 (FOUNDATION FIELDBUS)
Operating Instructions, 08/2014, A5E32221411-AC
Parameter Name
Introduction
Language
Material
Response Rate
Units
Low Calibration Point
High Calibration Point
Wizard Complete
Vessel Shape (2.4.1.1.)
PV (volume/level) Units
(2.3.3.)
Level Unit (2.3.2.)
Maximum Volume (2.4.1.2.)
Dimension A (2.4.1.3.)
Dimension L (2.4.1.4.)
Loss of Echo (LOE) Timer
(2.3.6.)
Options/
Function
Values
NEXT
Continue with Wizard.
NEXT
Continue with current language.
LIQUID
MED
Medium =1 m/minute
M
meters
3.5
3.5 m (11.48 ft)
0.5
0.5 m (1.64 ft)
FINISH
Transfers Quick Start settings to
device.
PARABOLIC
Defines vessel shape.
ENDS
L
liters
M
meters
8000
8000 liters
0.8
0.8 m (2.62 ft)
6
6 m (19.68 ft)
120
120 seconds
to start normal operation.
Commissioning
6.3 Application examples
75