Emerson Net Safety Millennium Reference Manual page 39

Apm oil mist detector air particle monitor
Hide thumbs Also See for Net Safety Millennium:
Table of Contents

Advertisement

To select that the relay be de-energized under normal conditions wait five (5)
seconds for the next selection. If energized has been selected, a flashing YES will
confirm the selection.
6.
To select that the relay be de-energized under normal conditions, press the Setup
button or use the Reed switch to select this option.
If the relay is setup as required, wait five (5) seconds for the next selection.
If De-energized has been selected, a flashing YES will confirm the selection.
The display will now show Latch Status, followed by Latching YES?.
7.
To select that the relay be latched in its alarm state, press the Setup button or use
the Reed switch to select this option.
To select that the relay be non-latching, wait five (5) seconds for the next selection.
If latching has been selected, a flashing YES will confirm the selection.
8.
To select that the relay be non-latching, press the Setup button or use the Reed
switch to select this option.
If the relay is setup as required, wait five (5) seconds for the next selection. If non-
latching has been selected, a flashing YES will confirm the selection.
The message Set Alarm and then YES? will be displayed.
9.
Press the Setup button or use the Reed switch to select this option.
A flashing YES will confirm this selection. After the Set Alarm option has been chosen,
the message Coil Status will be displayed, followed by Energized YES?.
10.
To select that the relay be energized under normal conditions, press the Setup
button or use the Reed switch to select this option.
To select that the relay be de-energized under normal conditions, wait five (5)
seconds for the next selection. If energized has been selected, a flashing YES will
confirm the selection.
11.
To select that the relay be de-energized under normal conditions, press the Setup
button or use the Reed switch to select this option.
If the relay is setup as required, wait five (5) seconds for the next selection. If de-
energized has been selected, a flashing YES will confirm the selection.
The display will now show Latch Status, followed by Latching YES?.
12.
To select that the relay be latched in its alarm state, press the Setup button or use
the Reed switch to select this option.
To select that the relay be non-latching, wait five (5) seconds for the next selection.
If latching has been selected, a flashing YES will confirm the selection.
13.
To select that the relay be non-latching, press the Setup button or use the Reed
switch to select this option.
Programming
31