Additional Parameters - Siemens Sitrans LR400 Instruction Manual

Hide thumbs Also See for Sitrans LR400:
Table of Contents

Advertisement

1.8 Application Type (F - Liquid [process])
Sets the use of the vessel
Value
Select Silo1 (solids) for solids with high reflectivity. Select Silo2 (solids) for solids with low
reflectivity, typically used for cement. In most cases, you set one of the pre-specified
applications. User vessels can be programmed using special configurations that deviate
from the factory specified models. They are designed for special applications loaded at
the factory or by trained service personnel.
The following parameters cannot be accessed when you set a user vessel
Note:
(User tank1 or User tank2):
• Parameter 4.2.2.2 (Surface)
• Parameter 4.2.2.5 (Filling Speed)
• Parameter 4.2.2.6 (Reflectivity)
• Sensor Parameters 4.2.3.1 (Sensor Damping)
• 4.2.3.2 (Multiple Echoes)
• 4.2.3.3 (Echo Motion)
• 4.2.3.4 (Window Tracking)
• 4.2.3.5 (Tank Empty Detect)
The parameters that remain under 4.2.2.x will be renumbered. See page 26 for more
information on parameter renumbering.

Additional Parameters

2. Display
2.1 Multi-display (F = level in m
Two-line display shows two measured values. The values to be shown are set using
Parameter 4.5. 1 . 1 (Line 1 Local) and in Parameter 4.5.1.4 (Line 2 Local).
2.2 Level (F = m)
Current level of material (set unit using Length Unit in Auto-Setup)
3
2.3 Volume (F = m
)
Volume of material (set unit using Parameter 4.1.2 [Volume Unit])
7ML19985FH06
SITRANS LR400 (7ML5421) – INSTRUCTION MANUAL
Liquid (store) [7ML5421 version]
Liquid (process) [7ML5421 version]
Silo1 (solids) [solids with high reflectivity]
Silo2 (solids) [solids with low reflectivity]
User tank1
User tank2
Signal to noise ratio in db)
Page 29

Advertisement

Table of Contents