...5 CONFIGURATION MODE
...5.6 Level A – Control Configuration
A. 0 3
PVFA
NONE
A. 0 4
dF. O P
0
•1
A. 0 5
OP. H I
100
•1
A. 0 6
OP. L 0
0
•2
A. 0 7
OP1H
100. 0
•2
A. 0 8
OP2H
100
•1
Displayed only if a single output type is selected.
•2
Displayed only if a heat/cool output type is selected.
84
Process Variable Fail Action
Determines controller output when the process variable input fails.
No action
NONE
Put into Manual mode
HOLd
Put into Manual mode and select default output
dFLt
Default Output
This output is used in conjunction with Power Recovery mode 8 and
Process Variable Fail action.
[0 to 100%] (–100% to +100% for heat/cool)
Output High Limit – Single Output Control
Limits the high level of the control output in automatic mode. If the control
output is above this limit when automatic mode is selected, the current
output value becomes the high limit until the value falls below the limit set.
[0.0 to 100.0%]
Output Low Limit – Single Output Control
Limits the low level of the control output in automatic mode. If the control
output is below this limit when automatic mode is selected, the current
output value becomes the low limit until the value rises above the limit set.
[0.0 to 100.0%]
Output 1 (Heat) High Limit – Heat/Cool Control
Limits the high level of control output 1 in automatic mode. If the control
output is above this limit when automatic mode is selected, the current
output value becomes the high limit until the value falls below the limit set.
[0.0 to 100.0%]
Output 2 (Cool) High Limit – Heat/Cool Control
Limits the high level of control output 2 in automatic mode, when
'reverse-direct' or 'direct-reverse' control action selected in the Basic
Configuration level. If the control output is above this limit when
automatic mode is selected, the current output value becomes the high
limit until the value falls below the limit set.
[0.0 to –100.0%]
Continued...
–100%
OP2
OP1
OP2H
0
A.03...A.08
+100%
0