IUH-F117-V1-*
Commissioning
Note!
Hexadecimal format
In the examples, hexadecimal values are displayed in .03 format. A period is
followed by two characters of hexadecimal code.
.03
= <ETX>
hex
.41
= A
hex
Commissioning the IDENTControl Compact Control Interface
1. On the PC, open a terminal program (e. g. "Hyperterminal" or the command in-
put window of the "RFIDControl" software supplied with the control interface).
2. Use the terminal program to set the interface configuration to
38400 baud,
8 data bits,
no parity,
1 stop bit,
no handshake
protocol: <CHCK><ETX>
3. Switch the device operating voltage off and on.
When the voltage is switched on, the message below appears on the
terminal:
20b.03
2 = Status
0 = IDENTControl channel
b = checksum
.03 = <ETX> = final symbol
The communication from the device to the terminal program functions. The
device is ready for operation.
4. Send the version command VE to the device as confirmation.
The device name, item number and software version of the control
interface and the read/write head are displayed.
Example:
Control interface
00(C) P+F IDENT IC-KP2-2HRX-2V1 #204980 1831464 05/03/10
<CHCK><ETX>
Read/write head
01 IUH-F117-V1 #206057 R010500-F010103 1831569 05/19/10
<CHCK><ETX>
(The software number and the software date may differ. For a description of
the VE command, read the "System commands" section in your control
interface manual.)
If you receive a different response, communication between your PC and the
device has failed. Check the installation and repeat the steps for commissioning
the device.