1.2 Functionality
The integration operation is as follow:
From the BACnet system point of view, after the start up process, the gateway reads
continuously the points configured to be read by polling and also performs all the
subscriptions (COV) requests for points configured to be read by subscription, and updates
in memory all the values received from the BACnet system. These values received from
BACnet become available to be read by the ASCII system in any moment.
From the ASCII system point of view, after the start up process of the gateway, IntesisBox
waits for any query (ASCII messages requesting readings of points or ASCII messages
requesting writings of points), and acts according to the message received. See ASCII
interface section for details about this ASCII messages.
Also, whenever a point changes of value (due to a change in the BACnet point associated)
the gateway will send an ASCII message informing about new value for the point, but only if
the point is configured to send this type of spontaneous messages.