5.1.4 Saving the configuration

When the configuration of the project is finished follow the next steps:
1. Click the button Save. Once accepted the pop-up message, that will save the project
in the folder on hard disk (more information in LinkBoxBacnet Manual).
2. You will be prompted to generate the configuration file to be sent to the gateway,
a. If YES is selected, the binary file (Modbus TCP.LBOX) containing the
configuration for the gateway will be generated and saved also into the
project folder.
b. If NO is selected the binary file needs to be created before following the next
steps. To do so open the Configuration window (section 5.1) and restart from
step 1
3. A pop-up message will show up asking if you want to preserve the Object
instance numbers. BE CAREFUL using this feature.
a. If NO is selected all the object instance numbers for the points will be
automatically reconstructed and thus loosing previous instance numbers, if
defined. ONLY USE this option for a brand new configuration not
previously running in the gateway and therefore not yet integrated into the
BACnet system
b. Select Yes for configurations previously running in the gateway and
already integrated into the BACnet system that had been extended with
a few more points that must respect the previously defined object
instance numbers. All the points with object instance numbers defined will
be respected. LinkBoxBacnet will automatically assign object instance
numbers to ones without it.
4. As the final step, a pop-up message will ask if you want to see the BACnet points list
report, If you select Yes, a text file called Modbus TCP- BACNET OBJECT LIST.TXT
will be generated and saved into the project folder containing a report of all the
point's BACnet information (for informative purposes at user level). The file will be
also opened in the notepad, it looks like this:
ObjIdent
00000000
00000001
04194304
04194305
04194306
08388608
08388609
12582912
12582913
12582914
12582915
12582916
16777216
16777217
20971520
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
®
IntesisBox
is a registered trademark of Intesis Software SL
ObjType
OInst ObjName
0-AI
0000 AI_1_read
0-AI
0001 AI_2_read
1-AO 0000 AO_1_read_write
1-AO 0001 AO_2_read
1-AO 0002 AO_3_write
2-AV
0000 AV_1_read_write
2-AV
0001 AV_2_read
3-BI
0000 Communication Error Dev.1
3-BI
0001 BI_1_read
3-BI
0002 BI_2_read
3-BI
0003 BI_10
3-BI
0004 BI_11
4-BO 0000 B0_1_read_write
4-BO 0001 BO_2_read_write
5-BV
0000 BV_1_read_write
User's Manual r1 eng
URL
http://www.intesis.com
Email
info@intesis.com
tel
+34 938047134
24 / 27

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IBOX-BAC-MBTCP-100 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Ibox-bac-mbtcp-aIbox-bac-mbtcp-b

Table of Contents