IntesisBox
BACnet/IP Server - Modbus TCP Master
Description
BACnet object name for the signal. This name is included into the BACnet's
Object_name property for the point and it will be collected by any BACnet
explorer.
Restrictions
Maximum 30 characters
Edit mode
Text edit
Comments
Recommended to give a descriptive name to each point with indication of
the Modbus TCP slave/register associated
Description
BACnet object type for the signal.
Values
Edit mode
Single / Multiple Values selection.
Comments
Edit using the mouse right-button-click pop-up menu
Description
BACnet object instance number for the point. It can be manually entered by
the user or can be automatically assigned by LinkBoxBacnet when saving the
configuration (section 5.1.4)
Restrictions
All the object instance numbers for objects of the same type must be
different
Edit mode
Text edit or AutoEnumeration
Comments
It is recommended to let LinkBoxBacnet assign automatically object instance
numbers for the points
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
®
IntesisBox
is a registered trademark of Intesis Software SL
Bac.Name
Bac.Type
AI = Analog Input.
AO = Analog Output.
AV = Analog Value.
DI = Digital Input.
DO = Digital Output.
DV = Digital Value.
MI = Multistate Input.
MO = Multistate Output.
MV = Multistate Value.
Bac.ID
URL
Email
tel
User's Manual r1 eng
http://www.intesis.com
info@intesis.com
+34 938047134
21 / 27