Discharge Time; Installation - Danfoss 176F6492 Installation Instructions Manual

In-bottom/out-back cooling kit for vlt parallel drive modules vlt series fc 102, fc 202, and fc 302

Advertisement

Installation Instructions
Lower duct assembly
1
Gasket between the top plate and the module (1)
2
Top plate between module and lower duct (1)
3
Gasket, top side plate (2)
4
Gasket, upper strip on front side of duct enclosure (1)
5
Gasket between front plate and access plate (2)
6
Access plate (2)
7
Front plate (1)
8
Gasket, lower strip on front side of duct enclosure (1)
9
Gasket between top plate and lower duct enclosure (1)
10
Top side plate (2)
11
Duct enclosure (1)
12
Gasket, side rail on front side of duct (2)
13
Gasket between grill and lower duct enclosure (1)
14
Bracket (3)
15
Grill (1)
16
Screw/washer assembly for bracket (3)
17
Gasket between grill and gland plate (1)
18
Base cover plate (2)
19
Gasket between the base cover plate and the base plate
(2)
Nuts, M5 (47) and M6 (3)
Illustration 1.2 Lower Duct Assembly for 1 Drive Module
2
In-bottom/Out-back Cooling Kit for VLT®
Parallel Drive Modules
VLT® Series FC 102, FC 202, and FC 302
Safety
WARNING

DISCHARGE TIME

The frequency converter contains DC-link capacitors, which
can remain charged even when the unit is off. High voltage
can be present even when the warning indicator lights are
off. Failure to wait 20 minutes after power has been
removed before performing service or repair work, could
result in death or serious injury.

Installation

If both a bus bar kit and a back-channel cooling kit are
being installed in the cabinet, install the back-channel
cooling kit first.
APPROVALS AND CERTIFICATIONS
This VLT
UL 508C compliant. These installation instructions describe
how to install the back-channel cooling kit which, if
followed, meet specific agency approvals and certifications.
Seek agency approvals or certifications apart from Danfoss if
designing and building other configurations.
APPLYING GASKETS
This kit contains gaskets to ensure a proper seal between
metal parts. Before adhering a gasket to a part, check that
the part matches the gasket and that no holes are covered.
Remove paper backing and place the sticky side on the part.
Danfoss A/S © 04/2016 All rights reserved.
Stop the motor.
Disconnect the AC mains, permanent magnet type
motors, and remote DC-link supplies, including
battery back-ups, UPS, and DC-link connections to
other frequency converters.
Wait 20 minutes for the capacitors to discharge fully,
before performing any service or repair work.
Measure the voltage level to verify full discharge.
®
Parallel Drive Modules back-channel cooling kit is
MI92L102