System And Utility Connections; Vacuum Connections; Cooling Water - Agilent Technologies HS-16 Instruction Manual

High throughput diffusion pumps
Hide thumbs Also See for HS-16:
Table of Contents

Advertisement

System and Utility Connections

WARNING
Utility failure can cause overheating, damage to the equipment and explosion. Design your system to
protect personnel and property from these hazards.

Vacuum Connections

The pump body must be installed vertical and plumb.
Check that the mating flange on the system is horizontal
o
±1
. If this condition is not met, correct the system mount
before installing the pump.
To make the vacuum system connection:
1. Wipe the O-ring seals with a clean cloth lightly
moistened with diffusion pump fluid. Do not use
solvents.
2. Install the O-ring in its groove. Be careful not to
damage the sealing surface with cuts, nicks, or
scratches.
3. Raise the pump using a lifting apparatus with
sufficient capacity. Pump weights are given in Table 4
on page 12.
4. Align the bolt holes of the flanges and assemble the
bolts.
5. Tighten the bolts evenly and compress the O-ring seal
until light contact is achieved between the metal
flanges.
6. Make a tightness check of the fill and drain plugs and
the sight glass assembly. Refer to the appropriate
outline drawings, Figure 6 on page 15 through
Figure 9 on page 18. Apply light to medium torque,
just enough to visually compress the gaskets.
NOTE
Over time, minute leaks may develop
through the gaskets. These leaks may
only be detectable with extremely
sensitive mass spectrometer leak
detectors.
High Throughput Diffusion Pumps
21

Cooling Water

To connect cooling water HS-16/20:
1. Connect the cold cap cooling coil and all body and
foreline cooling in series except the Quick Cool coil
(see the following paragraph) as shown in Figure 10.
Refer to Table 4 on page 12 for the cooling water
flowrate for your pump type. Higher flows will not
harm the pump.
2. If the diffusion pump is being cooled by a
recirculating water system, ensure the system is
capable of:
Adequate cooling and heat exchange to ensure a
continuous inlet temperature of 60 to 80 °F (16 to
27 °C).
Maintaining an adequate flow rate to ensure the
exit water temperature does not exceed 130 °F
(54 °C).
Parallel connections should be employed when the water
pressure is low or if the discharge temperature routinely
o
exceeds 130
F.
Figure 10 HS-16/20 Cooling Water Connections
Return

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hs-32Nhs-35Hs-20

Table of Contents