• Forecasting method: by activation of the forecast method, the system
will automatically predict the heating start-up time necessary to reach the
desired room temperature at desired time (all heat emitter types).
• Maximum floor temperature: the default setting is 35 °C (electrical floor
heating).
• Regulation type: only in connection with electrical heating systems.
Note! Use pincode [0044] to change between the following regulation types:
Room sensor (regulates only by room temperature) - if only Danfoss Link™ RS is
fitted (hydronic floor heating) or Danfoss Link™ RS + Danfoss Link™ FT (electrical
heating).
Floor sensor (regulates only by floor temperature ) - if only Danfoss Link™ FT/S
is fitted.
Combined room/floor (ensures min. floor temperature and regulates room
temperature in parallel) - Danfoss Link™ RS + Danfoss Link™ FT/S is fitted.
In case of hydronic floor heating, be aware if a certain max. floor temperature is
given by the floor manufacturer. This can be assured by fitting a thermostatically
controlled mixing shunt.
Danfoss Heating Solutions
Danfoss Link™ CC
VISGL702
06/2013