Siemens SIMATIC ET 200SP Manual page 53

Analog input module
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Technical specifications
6.1 Technical specifications
Operational and basic error limits for resistance thermometers
Error limits for resistance thermometers
Operational limit (in the entire temperature range, in relation to input
range)
Basic error limit (operational limit at 25 °C, in relation to input range)
Operational and basic error limits for thermocouples
Error limits for thermocouples
Operational limit for thermocouples (in the entire temperature range)
Basic error limit for thermocouples (operational limit at 25 °C)
Overall error limits when using internal compensation
The indicated error limits apply as of the following temperatures:
1
Dimension drawing
See manual ET 200SP BaseUnits
(http://support.automation.siemens.com/WW/view/en/58532597/133300)
52
Pt 100, Pt 200, Pt 500, Pt 1000 standard
Pt 100, Pt 200, Pt 500, Pt 1000 climatic
Ni 100, Ni 120, Ni 200, Ni 500, Ni 1000 standard and climatic
Cu 10
Pt 100, Pt 200, Pt 500, Pt 1000 standard
Pt 100, Pt 200, Pt 500, Pt 1000 climatic
Ni 100, Ni 120, Ni 200, Ni 500, Ni 1000 standard and climatic
Cu 10
Operational limit (in the entire temperature range at static thermal
state, ambient temperature change < 0.3 K/min)
Basic error limit (operational limit at 25 °C at static thermal state,
ambient temperature change < 0.3 K/min)
Thermocouple type T: -200 °C
Thermocouple type K: -100 °C
Thermocouple type B: +700 °C
Thermocouple type N: -150 °C
Thermocouple type E: -150 °C
Thermocouple type R: +200 °C
Thermocouple type S: +100 °C
1
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
±1.0 K
± 0.25 K
± 0.4 K
±1.5 K
± 0.6 K
± 0.13 K
± 0.2 K
±1.0 K
±1.5 K
±1 K
± 2.5 K
±1.5 K
Manual, 09/2018, A5E03573289-AE