Table B- 15
Thermocouple type E
Type E
Values
in °C
Dec.
Hex.
> 1200.0
32767
7FFF
1200.0
12000
2EE0
:
:
:
1000.1
10001
2711
1000.0
10000
2710
:
:
:
-270.0
-2700
F574
< -270.0
-32768
8000
Table B- 16
Thermocouple type J
Type J
Values
in °C
Dec.
Hex.
> 1450.0
32767
7FFF
1450.0
14500
38A4
:
:
:
1200.1
12001
2EE1
1200.0
12000
2EE0
:
:
:
-210.0
-2100
F7CC
< -210.0
-32768
8000
Table B- 17
Thermocouple type K
Type K
Values
in °C
Dec.
Hex.
> 1622.0
32767
7FFF
1622.0
16220
3F5C
:
:
:
1372.1
13721
3599
1372.0
13720
3598
:
:
:
-270.0
-2700
F574
< -270.0
-32768
8000
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Manual, 09/2018, A5E03573289-AE
Type E
Values
in °F
Dec.
Hex.
> 2192.0
32767
7FFF
2192.0
21920
55A0
:
:
:
1832.1
18321
4791
1832.0
18320
4790
:
:
:
-454.0
-4540
EE44
< -454.0
-32768
8000
Type J
Values
in °F
Dec.
Hex.
> 2642.0
32767
7FFF
2642.0
26420
6734
:
:
:
2192.1
21921
55A1
2192.0
21920
55A0
:
:
:
-346.0
-3460
F27C
< -346.0
-32768
8000
Type K
Values
in °F
Dec.
Hex.
> 2951.6
32767
7FFF
2951.6
29516
734C
:
:
:
2501.7
25017
61B9
2501.6
25016
61B8
:
:
:
-454.0
-4540
EE44
< -454.0
-32768
8000
Representation of analog values
B.5 Representation of analog values for thermocouples
Type E
Values
in K
Dec.
> 1473.2
32767
1473.2
14732
:
:
1273.3
12733
1273.2
12732
:
:
3.2
32
< 3.2
-32768
Type J
Values
in K
Dec.
> 1723.2
32767
1723.2
17232
:
:
1473.3
14733
1473.2
14732
:
:
63.2
632
< 63.2
-32768
Type K
Values
in K
Dec.
> 1895.2
32767
1895.2
18952
:
:
1645.3
16453
1645.2
16452
:
:
3.2
32
< 3.2
-32768
Range
Hex.
7FFF
Overflow
398C
Overrange
:
31BD
31BC
Nominal range
:
0020
8000
Underflow
Range
Hex.
7FFF
Overflow
4350
Overrange
:
398D
398C
Nominal range
:
0278
8000
Underflow
Range
Hex.
7FFF
Overflow
4A08
Overrange
:
4045
4044
Nominal range
:
0020
8000
Underflow