Article number
Input ranges (rated values), resistors
0 to 150 ohms
•
Input resistance (0 to 150 ohms)
•
0 to 300 ohms
•
Input resistance (0 to 300 ohms)
•
0 to 600 ohms
•
Input resistance (0 to 600 ohms)
•
0 to 3000 ohms
•
Input resistance (0 to 3000 ohms)
•
0 to 6000 ohms
•
Input resistance (0 to 6000 ohms)
•
PTC
•
Input resistance (PTC)
•
Thermocouple (TC)
Temperature compensation
–
parameterizable
–
Reference channel of the module
–
internal comparison point
–
Reference channel of the group
–
Number of reference channel groups
–
fixed reference temperature
Cable length
shielded, max.
•
Analog value generation for the inputs
Measurement principle
Integration and conversion time/resolution per
channel
Resolution with overrange (bit including
•
sign), max.
Integration time, parameterizable
•
Basic conversion time, including integration
•
time (ms)
–
additional processing time for wire-
break check
–
additional power line wire-break check
Interference voltage suppression for inter-
•
ference frequency f1 in Hz
Conversion time (per channel)
•
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Manual, 09/2018, A5E03573289-AE
6ES7134-6JD00-0CA1
Yes; 15 bit
1 MΩ
Yes; 15 bit
1 MΩ
Yes; 15 bit
1 MΩ
Yes; 15 bit
1 MΩ
Yes; 15 bit
1 MΩ
Yes; 15 bit
1 MΩ
Yes
Yes
Yes; with BaseUnit type A1
Yes
4; Group 0 to 3
Yes
200 m; 50 m with thermocouples
integrating (Sigma-Delta)
16 bit
Yes
2 ms; In the ranges resistance thermometers,
resistors and thermocouples
2 ms; for 3/4 wire transducer (resistance ther-
mometer and resistor)
16.6 / 50 / 60 Hz
180 / 60 / 50 ms
Technical specifications
6.1 Technical specifications