Measures; Ats Settings - Eaton EATS16N Installation And User Manual

Hide thumbs Also See for EATS16N:
Table of Contents

Advertisement

2. Presentation

2.4.2 Measures

Output current
(default display)
Output voltage
Input voltage : S1
(default display only when S1 voltage is out of tolerance)
Input frequency: S1
(default display only when S1 frequency is out of tolerance)
Input voltage : S2
(default display only when S2 voltage is out of tolerance)
Input frequency: S2
(default display only when S2 frequency is out of tolerance)
S1 and S2 phase shift
(available only when S1 and S2 are not synchronized)
2.5

ATS settings

OUTPUT: Sets voltage thresholds
-
ALARM: Silents alarm
-
SENSITIVITY (mainly for LIA UPS): Sets
Sensitivity mode for input mains detection.
-
P SOURCE: Sets the priority source
TRANSFER:
Page 6
200 V - 208 V - 220 V - 230 V (default) - 240 V
ON: normal beep in warning or fault mode, by default
OFF: silent.
Std: Normal Sensitivity, by default
Lo: Low Sensitivity, for compatibility with distorted
waveform.
Sc.1: Priority on Source 1, by default
Sc.2: Priority on Source 2
Std: no additional break even if S1 and S2 are not
synchronized, by default
Gap: additional break during transfer if S1 and S2 are
not synchronized.
EATS16_EN