Warranty in tHe Switch elevator disconnect users should observe at all times . This terms anD conDitions of sale is tHe sole Warranty of eaton. summary is not comprehensive . It is assumed the Elevator Control...
. It is also easy to meet Code requirements for selec- Isolated neutral lug (oversized 200% rated neutral option available • tive coordination in a fully fused system . The Eaton Elevator Control where required by excessive non-linear loads) ES Switch utilizes Class J fuses that easily coordinate with any Fire Alarm Voltage Monitoring Relay (to monitor Shunt Trip Voltage) •...
120 Vac supply originat- Arizona, Oregon, and Texas requirements to prevent “nuisance” fire ing in the Eaton Elevator Control ES switch . Current to the shunt-trip alarms by over-riding the “Control Power not Available” signal when...
“+” marker will change the option A switch logic. Removal has the effect of disabling the bat- tery lowering device when the switch is in the tripped position. Field installer must ensure this meets all local codes before removal. Figure 2. Options R1 and F3. eaton corporation www.eaton.com...
Page 6
Elevator Control ES Switch Technical Data TD00801003E Effective November 2011 Typical Control with Wiring Options for Fire Safety Interface (Cont.) Figure 3. Option R2 eaton corporation www.eaton.com...
Page 7
Elevator Control ES Switch Technical Data TD00801003E Effective November 2011 Typical Control with Wiring Options for Fire Safety Interface (Cont.) Figure 4. Options R1 and F1 eaton corporation www.eaton.com...
Page 8
SWITCH LOGIC TABLE, REMOVAL HAS THE EFFECT OF DISABLING THE BATTERY LOWERING DEVICE WHEN THE SWITCH IS IN THE TRIPPED POSITION. FIELD INSTALLER MUST ENSURE THIS MEETS ALL LOCAL CODES BEFORE REMOVAL. Figure 5. Options R2 and F1 eaton corporation www.eaton.com...
Page 9
Elevator Control ES Switch Technical Data TD00801003E Effective November 2011 Figure 6. Option F3. eaton corporation www.eaton.com...
Page 10
Elevator Control ES Switch Technical Data TD00801003E Effective November 2011 Figure 7. Option F1 eaton corporation www.eaton.com...
Elevator Control ES Switch Technical Data TD00801003E Effective November 2011 Figure 8. Voltage Monitoring with B-Contact Option. eaton corporation www.eaton.com...
Page 12
Elevator Control ES Switch Technical Data TD00801003E Effective November 2011 Figure 9. Common Wiring Scheme for AZ, TX, and OR Applications. Elevator Control Option B Detail. eaton corporation www.eaton.com...
(Option B) work? tion . The “B” Option provides a second set of auxiliary contacts that are An annual review of the Eaton Elevator Control ES Switch is rec- • mechanically interlocked to the main switch . These contacts are ommended .
Page 14
9. Does the switch require any Eaton Elevator Control ES void the Eaton UL listing . One exception is the B-option . It can be periodic maintenance? ordered and field installed; the part number is ECSBKIT . While no specific maintenance is called for, it is always a good prac- 14.
Page 15
Elevator Control ES Switch Technical Data TD00801003E Effective November 2011 16. Can the Eaton Elevator Control ES switch be used in an application where no fire alarm exists and can a smoke detector be connected instead? No, this is not in accordance with the fire code . Commercial smoke detectors must be connected through the FACP .
Page 16
. The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton . NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING...