Summary of Contents for Eaton Edison Cooper Power Series
Page 1
COOPER POWER Vacuum Switches SERIES Effective February 2017 MN230007EN Supersedes November 2016 Edison™ Single-Phase Vacuum Capacitor Switch Installation and Operation Instructions...
CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to...
FOR LIFE FOR LIFE Eaton meets or exceeds all applicable industry standards relating to product safety in its Cooper Power™ series products. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service.
When additional information is desired to satisfy a problem not cov ered sufficiently for the user’s purpose, please contact your Eaton’s Cooper Power series product representative. Acceptance and initial inspection Each capacitor switch is completely assembled, inspected, tested, and adjusted at the factory.
Edison™ Single-Phase Vacuum Capacitor Switch Ratings and specifications Check switch ratings before installation Ratings The Edison capacitor switch must be applied within its All ratings meet or exceed values in IEEE Std C37 .66™-2005 specified ratings. Check data plate ratings and compare with standard for a distribution-class switch, where applicable.
80–100 ms for each practices when installing or operating this equipment . operation. Eaton requires a 10-second cool-down period Failure to comply can result in death, severe personal between open and close operations to ensure the injury and equipment damage .
Schematic diagrams of switch actuators wired for two- and three-wire controls are shown in Figure 2. Accessories are shown with dashed lines. These diagrams apply only for alternating current (ac) control voltage. For direct current (dc) control voltage please contact your Eaton’s Cooper Power series product representative. Figure 2 . Typical connection diagrams (switch shown in OPEN position)
Edison™ Single-Phase Vacuum Capacitor Switch Switch operation Electrical operation Contact position indication The switch may be opened and closed electrically by The yellow operating handle is also used as a contact applying rated control voltage to the proper terminals of position indicator.
Need help?
Do you have a question about the Edison Cooper Power Series and is the answer not in the manual?
Questions and answers