Warning - Eaton EATS16N Installation And User Manual

Hide thumbs Also See for EATS16N:
Table of Contents

Advertisement

2. Presentation
2.6

Warning

For Fault, refer to troubleshooting section 6.1.
Event
Overload
Unsynchronized sources
Source 1 or Source 2 power loss
Source 1 or Source 2 voltage out
of tolerance
Source 1 or Source 2 frequency
out of tolerance
Source 1 and Source 2 quality
Page 8
Example of displays
Rootcause
Load is over nominal rating
Remove some of the equipment from
the ATS.The ATS continues to operate,
but may shutdown if the load increases.
The alarm resets when the condition
becomes inactive.
One source N and L are reversed
S1 ansd S2 are fed by different phase
(L1/L2/L3)
S1 and S2 frequency are different
One of the source is missing,
The ATS power on the load with the
source that is present.
One of the source voltage is out of
tolerance.
The display shows the voltage measure
of the faulty source.
One of the source frequency is out of
tolerance.
The display shows the frequency
measure of the faulty source.
The sources are outside ranges so that
it generates too many transfers within a
short period of time.
The alarm resets when the condition
becomes inactive.
EATS16_EN