Wall Installation; Instructions - Eaton EATS16N Installation And User Manual

Hide thumbs Also See for EATS16N:
Table of Contents

Advertisement

3.5

Wall installation

Follow steps 1 to 2 for module mounting on the wall.
2
2
3.6

Instructions

1. E levated Operating Ambient - If installed in a closed or multi-unit rack assembly, the operating ambient
temperature of the rack environment may be greater than room ambient. T herefore, consideration
should be given to installing the equipment in an environment compatible with the maximum ambient
temperature (Tmax) specified by the manufacturer.
2. Reduced Air Flow - Installation of the equipment in a rack should be such that the amount of air flow
required for safe operation of the equipment is not compromised.
3. Mechanical Loading - Mounting of the equipment in the rack should be such that a hazardous condition is
not achieved due to uneven mechanical loading.
4. Circuit Overloading - Consideration should be given to the connection of the equipment to the supply
circuit and the effect that overloading of the circuits might have on overcurrent protection and supply
wiring. Appropriate consideration of equipment nameplate ratings should be used when addressing this
concern.
5. R eliable Earthing - Reliable grounding of rack-mounted equipment should be maintained. Particular
attention should be given to supply connections other than direct connections to the branch circuit (e.g.
use of power strips).
EATS16_EN
1
1
3. Installation for ATS
Page 11