Only use the frequency inverter if the rated connection and setup values specified by the manu-
facturer are met.
Provide appropriate tools as may be required for performing all work on the frequency inverter
properly.

2.8.3 Ear protectors

The frequency inverter produces noise. Due to noise development, frequency inverters should
only be installed in normally unstaffed areas.
Noise emission in operation is < 85 dB(A) in the case of sizes 1 through 7.
Noise emission in operation is approx. 86 dB(A) in the case of size 8. Ear protectors must be used
when staying near the frequency inverter.

2.9 Organizational measures

2.9.1 General

Train your staff in the handling and use of the frequency inverter and the machine/plant as well
as the risks involved.
Use of any individual parts or components of the frequency inverter in other parts of the opera-
tor's machine/plant is prohibited.
Optional components for the frequency inverter must be used in accordance with their designated
use and in compliance with the relevant documentation.

2.9.2 Use in combination with third-party products

Please note that Bonfiglioli Vectron GmbH will not accept any responsibility for compatibility with
third-party products (e.g. motors, cables or filters).
In order to enable optimum system compatibility Bonfiglioli Vectron GmbH offers components fa-
cilitating commissioning and providing optimum synchronization of the machine/plant parts in op-
eration.
If you use the frequency inverter in combination with third-party products, you do so at your own
risk.

2.9.3 Handling and installation

Do not commission any damaged or destroyed components.
Prevent any mechanical overloading of the frequency inverter. Do not bend any components and
never change the isolation distances.
Do not touch any electronic construction elements and contacts. The frequency inverter is
equipped with components which are sensitive to electrostatic energy and can be damaged if han-
dled improperly. Any use of damaged or destroyed components will endanger the machine/plant
safety and shall be considered as non-compliance with the applicable standards.
Only install the frequency inverter in a suitable operating environment. The frequency inverter is
exclusively designed for installation in industrial environments.
If seals are removed from the case, this can result in the warranty becoming null and void.

2.9.4 Electrical connections

The five safety rules must be complied with.
Never touch live terminals. In sizes 1 through 7, the DC-link may have dangerous voltage levels
up to 3 minutes after shutdown. In size 8, the DC-link may have dangerous voltage levels up to
10 minutes after shutdown.
When performing any work on/with the frequency inverter, always comply with the applicable na-
tional and international regulations/laws on work on electrical equipment/plants of the country in
which the frequency inverter is used.
The cables connected to the frequency inverters may not be subjected to high-voltage insulation
tests unless appropriate circuitry measures are taken before.
Only connect the frequency inverter to suitable supply mains. The frequency inverter may be op-
erated in TN, TT and IT grid types. Precautions must be taken for operation in IT grids, see Chap-
ter 7 "Electrical installation". Operation in a corner-grounded TN grid shall not be permissible.
The five safety rules
When working on/in electrical plants, always follow the five safety rules:
1
Disconnect
2
Secure to prevent restarting
3
check for absence of voltage,
03/18
AGL-STOV0-01SV0-06
11