10.1.4
STO Direct Stop w/ Feedback to PLC w/ error exclusion "short
circuit" in cabinet
The application circuit shows a drive control system with PLC and safety module according to EN ISO
13849-1 PL d and Category 3 or IEC 61508 SIL 2. Safety control equipment with one enable path and
interconnection line is implemented instead of safety control equipment with two enable paths.
Comply with the following conditions:
Safety control equipment and inverter have to be placed in the same cabinet.
Error exclusion in case of short circuit has to be ensured for wiring between safety control
equipment and inverter (for example insulated conductor).
30
AGL-STOV0-01SV0-06
03/18