5 Start Up
Leveling Speed Priority is Selected and the Nominal Speed Input is Not Assigned (d1-18 = 2, H1-
The drive runs at nominal speed (d1-19) when no speed selection input is set. When the leveling speed signal is set, the
drive decelerates to the leveling speed. The leveling speed signal has priority over all other speed signals.
CAUTION! This sequence can be risky if the speed selection doesn't work for some reason (broken wire, etc.)
I/O Signal Setup
Note: The default setting functions can be seen in the connection diagram on page 10.
Multi-Function Digital Inputs
Assign functions to each digital input terminal using the H1-
Multi-Function Digital Outputs
Determine the function for each digital output terminal with the H2-
parameters consists of three digits, where the middle and right digit determines the function, and the left digit sets the
output characteristics. The output characteristics can be either "Output as selected" (0) or "Inverse output" (1).
Multi-Function Analog Inputs
The function of each analog input can be assigned in the H3-
Multi-Function Analog Outputs
Use the H4-
levels.
Acceleration Ramp, Deceleration Ramp, and Jerk Settings
The acceleration and deceleration ramps are set in the parameters C1-01 and C1-02, while the jerk settings are set in the
C2-
parameters as shown in the figure below.
The way of setting these parameters and their setting units change with parameter o1-03 as shown below:
Accel/Decel Ramps C1-
Jerk Settings C2-
28
PDF compression, OCR, web optimization using a watermarked evaluation copy of CVISION PDFCompressor
DC Injection/
position lock
Speed
Safe disable
Up/Down
Leveling speed
parameters to set up the output value of the analog monitor outputs and to adjust the output signal
C2-02
Jerk Characteristic
at Accel End
Acceleration Ramp 1
C2-01
C1-01
Jerk Characteristic
at Accel Start
Deceleration Ramp 1
o1-03 = 0, 1, 2, 3, 4
Set in units of second as the time to accelerate from
zero to the rated speed, respectively as time to
decelerate from rated speed to zero.
Set in units of second as the time used to change the
accel/decel rate from zero to the accel/decel ramp
setting of C1-
and vice versa.
parameters.
parameters. The setting value of these
parameters.
C2-03
Jerk Characteristic
at Decel Start
C2-04
Jerk Characteristic
at Decel End
C1-02
Set in units of m/s
changing the speed.
Set in units of m/s
YASKAWA ELECTRIC TOEP C710616 33A YASKAWA AC Drive L1000A Quick Start Guide
DC Injection/
position lock
C2-05 Jerk below Leveling Speed
Leveling Speed
o1-03 = 5
2
as accel/decel rate used when
3
as the accel/decel change rate.
≠ 50)