Programmable Timer is Not Counting Down Per its Schedule

Problem
Programmable Timer is not counting down.
Cause
For Programmable Timer models, the timer's schedule is configured in the Primex Event Scheduler Pro software to the schedule
ID controller 24. The schedule is downloaded from the Event Scheduler Pro to the system Transmitter, allowing the Transmitter to
broadcast the schedule. This issue may be due the timer setting, the schedule download to the Transmitter(s), or the Transmitter
status.
Solution
1. From its setting panel, verify the PT/TC Switch (5) is set to the ON position.
At access the setting panel - from the back side of the clock remove the small rectangular access panel. Setting changes can
be made while the clock/timer is ON and changes will take effect within a few seconds.
2. From the Primex Event Scheduler Pro software, verify the schedule ID is set to controller 24.
3. Verify the schedule has been downloaded the local Transmitter(s) that are within range of a Programmable Timer.
4. Verify the Transmitter operating status. Refer to the Transmitter Troubleshooting topics.
If the issue cannot be resolved, additional troubleshooting is required. For further assistance, contact Primex Technical Support at
1-262-729-4860.