To register thermostatic heads in the controller:
1. A thermostat must be registered to a sufficient
number of channels to be able to control all
thermostatic heads in a room. A maximum of two
thermostatic heads can be registered per channel.
See section Uponor Smatrix Wave documentation
for more information.
2. Press and hold the OK button on the controller until
the LED for the first unregistered channel flashes
red. If all channels are registered to thermostats, the
LED flashes red and green.
3. Use buttons < or > to move the pointer (LED
flashes red) to the intended thermostat channel
(green LED). The LED flashed red and green.
If the first channel is full, move the pointer to the
next thermostat channel in line.
4. THERMOSTATIC HEAD T-162
4.1 Press and hold both - and + buttons on the
thermostatic head until the text CnF (configure)
and a communication icon is displayed.
The text Con is shown in the display, and the
selected channel LED in the controller turns
fixed green, when the registration is complete.
Note! If the text --- is shown in the
thermostatic head display the registration
failed. Repeat steps 2 through 3 and try
the next channel in line, in case two other
thermostatic heads already has been registered
to the current one.
5. Press one of the buttons on the controller and
repeat steps 3 through 4 until all thermostatic heads
are registered.
6. Press and hold the OK button on the controller
until the green LEDs turn off to end registration and
return to run mode.