Register thermostat and/or system device
to a controller
To register room thermostats and system devices (interface
etc.) to the controller:
Enter registration mode
11. Press and hold the OK button on the controller, for
about 3 seconds, until the LED for channel 1 (or the
first unregistered channel) flashes red.
Register a thermostat
12. Select a thermostat channel.
12.1 Use buttons < or > to move the pointer (LED
flashes red) to a preferred channel.
12.2 Press the OK button to select the channel for
registration. The LED for the selected channel
starts flashing green.
12.3 Repeat steps 12.1 and 12.2 until all channels to
be registered with the thermostat are selected
(LEDs flashing green).
Note! It is recommended to register all channels
to the thermostat at the same time.
13. Select a thermostat.
THERMOSTAT T-163 AS A THERMOSTAT, WITH
VARIOUS FUNCTIONS
13.1 Gently press and hold the registration button
on the thermostat, release when the LED starts
flashing green (located in the hole above the
registration button).
The selected channel LED in the controller turns
fixed green and the registration is complete.
THERMOSTAT T-161 AND T-165
13.1 Gently press and hold the registration button
on the thermostat, release when the LED on the
front of the thermostat starts flashing.
The selected channel LED in the controller turns
fixed green and the registration is complete.
THERMOSTATS T-166, T-168 AND T-169
13.1 Press and hold both - and + buttons (T-169
=
and ) on the thermostat until the text
CnF (configure) and a communication icon is
displayed.
The selected channel LED in the controller turns
fixed green and the registration is complete.
14. Repeat steps 12 and 13 until all available thermostats
are registered.
Register a system device (I-167 etc)
N O T E !
At least one thermostat must be registered before
registering a system device.
15. Make sure to be in registration mode (step 11).
U P O N O R S M AT R I X WAV E · Q U I C K G U I D E
QUICK GUIDE
15.1 Use buttons < or > to move the pointer to the
power LED (LED flashes red).
15.2 Press the OK button to enter system channel
registration mode. The power LED flashes
according to the pattern long blink, short pause,
long blink and channel 1 LED flashes red.
15.3 Select a system channel, see list below.
1 = Touch screen interface
2 = Relay module
3 = Public thermostat with outdoor sensor
4 = Public thermostat with heating/cooling
5 = Public thermostat with Comfort/ECO switch
15.4 Press the OK button to select system device
channel. The channel LED starts flashing green.
16. Select a system device matching the system channel.
INTERFACE I-167
16.1. Power up the interface and attach it to the
charger.
16.2. Follow the startup guide in the interface up until
registration.
16.3 Press Link Touch Screen to controller in the
Startup guide, or RF Link menu (Main menu >
Preferences), to initialize registration.
16.4 The interface gets registered to the controller.
The selected channel LED in the controller turns
fixed green and the registration is complete.
RELAY MODULE M-161
16.1 Press and hold the register button on the relay
module until the LEDs on the module start
flashing slowly.
The selected channel LED in the controller turns
fixed green and the LEDS on the relay module
start flashing fast again, to turn off a few seconds
later.
THERMOSTAT T-163 AS A SYSTEM DEVICE, WITH
VARIOUS FUNCTIONS
16.1 Gently press and hold the registration button
on the thermostat, release when the LED starts
flashing green (located in the hole above the
registration button).
The selected channel LED in the controller turns
fixed green and the registration is complete.
17. Repeat steps 15 and 16 until all available system devices
are registered.
Exit registration mode
18. Press and hold the OK button on the controller, for
about 3 seconds, until the green LEDs turn off to end
registration and return to run mode.
switch from contact or sensor input