Product Description

ANN-I/O LED Driver Module

The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including as an interface with most customized
graphic annunciators. The ANN-I/O can drive up to 40 LEDs. The module is provided with a plastic wall mount.

ANN-LED Annunciator Module

The ANN-LED and ANN-RLED annunciator modules provide LED annunciation of general system faults and input zones/points when
used with a compatible FACP. The ANN-LED module provides alarm (red), trouble (yellow) and supervisory (yellow) indication for up
to ten input zones or addressable points. The ANN-RLED provides alarm (red) indication for up to 30 input zones or addressable points.
Multiple ANN-(R)LED modules may be used for full system coverage.

ANN-RLY Annunciator Module

The ANN-RLY relay module provides 10 programmable Form-C relays when used with a compatible FACP.

1.7 Getting Started

The following is a brief summary of the minimal steps involved in bringing an ES-200 on-line:
Install backbox and main circuit board (refer to "Mounting the Backbox" on page 22)
Address and install intelligent devices (refer to the SLC Wiring Manual)
Enter autoprogramming (refer to "Autoprogram" on page 52)
Resolve programming conflicts
Go to point program to enter specific data (refer to "Point Program" on page 53). Use the right and left arrow keys to navigate
between devices.

1.8 Telephone Requirements and Warnings

1.8.1 Telephone Circuitry
Ringer Equivalence Number (REN) = 0.3A
AC Impedance: 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: loss of phone line voltage for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone
line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not
exceed five (5.0). To be certain of the number of devices that may be connected to the line as determined by the total RENs, contact the
telephone company to determine the maximum REN for the calling area.
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. If trouble
is experienced with this equipment, for repair or warranty information, please contact:
Manufacturer:
Product Model Number: ES-200X
FCC Registration Number: US:1W6AL03AEVOLX
Ringer Equivalence: 0.3A
NOTE: This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the FACP
door is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number
must be provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this
even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dial-
ing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment
attached to the same telephone line. If there are any questions concerning these instructions, consult the telephone company or a quali-
fied installer about installing the RJ31X jack and alarm dialing equipment. Refer to "IPOTS-COM Communicator" on page 30 for an
illustration of the proper installation of this equipment.
Important! The DACT must not be used to dial a phone number that is call-forwarded.
20
Honeywell International, Inc.
One Fire-Lite Place
Northford, CT 06472
(203) 484-7161
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018