7: Ann-I/O Led Driver Module - Fire-Lite Alarms MS-5UD Series Manual

Fire alarm control panels
Table of Contents

Advertisement

Installation
2.8.7 ANN-I/O LED Driver Module
The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including
as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40
LEDs. The following sections describe hardware installation. Refer to the section titled "ANN-
BUS" on page 80 for programming information.
2.8.7.1 ANN-I/O Board Layout
Figure 2.22 illustrates the ANN-I/O board showing locations of screw terminals for connection
to the FACP, pin connectors for connecting LEDs and the DIP switch for selecting the ANN-
BUS ID number.
2.8.7.2 Specifications
Max. ANN-BUS Voltage: 28 VDC
Max. Current:
Operating Temperature: 32
For indoor use in a dry location only
46
Terminals not used (future)
Figure 2.22 ANN-I/O Board Layout
Alarm: 200 mA
Standby: 35 mA
Each LED: 10 mA
o
F to 120
ANN-BUS Connector
o
o
o
F (0
C to 49
C)
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
ANN-BUS Devices
ANN-BUS (ID#)