3: Playback Button; Led Indicators; 1: Leds Visible With Backbox Door Closed (Refer To Figure - Fire-Lite Alarms FIRE COMMAND 25 Installation And Operating Instruction Manual

Voice evacuation
Table of Contents

Advertisement

LED Indicators

end of the voice recording, the unit automatically ends the message at the time out period selected. For dual
language recordings, it is recommended that the 60 second option be selected. The two 30 second recordings
should only be used for fire/nonfire or fire evacuation/fire clear messages.
For Dual Message Only - Follow all steps listed above except note that as soon as the 'Trouble Silence' key is
7.
pressed to signal the end of the first 30 second recording, the 'REC' LED starts flashing at a rapid rate of ½
second On and ½ second Off. This signals the start of the second record time. Begin recording immediately
and signal the end of the second recording by pressing the 'Trouble Silence' key. If you are not ready to
immediately record the second message when the LED begins flashing at the ½ second rate, cancel by press-
ing the 'Trouble Silence' key. This shuts off the 'REC' LED and stops all recording. When ready to record,
start the sequence beginning with Step 4. Skip over the first 30 second recording by pressing the 'Trouble
Silence' key twice in rapid succession. The green 'REC' LED will begin flashing at a ½ second rate, signal-
ing the start of the second 30 second message.
Disable recording by setting S5 switch 8 to the OFF position. The Trouble Silence key operation resumes.
8.
Playback the recorded messages for accuracy. This may be done via the 'Playback" key or by creating an
9.
alarm or evacuate condition. The Playback feature allows for reviewing the message locally via the FC-LPS
option module without generating the message through the amplifiers.
CAUTION! Be certain to slide the Record Bypass switch S2 to the Down position when recording is completed. This
!
will prevent accidental rerecording or deletion of the stored message(s). It is not possible to record with the S2
Record Bypass switch in the Down position.
4.1.3 Playback Button
The Playback button can be used to review the stored voice message(s). By connecting the optional Local Playback
Speaker Module, the message can be heard without transmitting it over the system speakers. Pressing the Playback
button will cause the following:
In a system set for one 60 second message, the message will play until the end or until the Playback button is
pressed a second time.
In a system set for two 30 second messages, the first message will play until the end or until the Playback but-
ton is pressed a second time, which will start the second message. The second message will play until the end
or until the Playback button is pressed to stop the message.
Note that the voice message will repeat according to the S1 DIP switch settings (see "S1 DIP Switch Settings" on
page 15). Refer to Figure 3-18, "Installation of Speaker Module," on page 31, for additional information.
4.2
LED Indicators
4.2.1 LEDs Visible with Backbox Door Closed (Refer to Figure 4-1 on page 32)
Power On
A green LED that remains on while the DC power source is within correct limits. If this indicator fails to light
under normal conditions, service the system immediately.
System Trouble
This yellow LED turns on steady to indicate that a fault or abnormal condition exists and that the VECP may be
inoperative.
Alarm
A red LED that turns on steady when either CMD1 or CMD2 inputs are triggered. The LED also turns on when
the Manual Evacuation switch is in the latched position.
Microphone Trouble
This yellow LED turns on steady when the supervised microphone connection is open.
Technical Manuals Online! - http://www.tech-man.com
Document #50580
Rev. C
firealarmresources.com
8/12/97
P/N 50580:C
33