Function Keys - Fire-Lite Alarms ES-200XC Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Programming
Language: This option allows the user to switch between English and French language text on the panel display.
Charger Enable: This option allows the user to install an external battery charger.
4XTM Supervision: This feature enables supervision of an installed 4XTMF Transmitter Module.
Remote Sync Enable: This feature controls the activation of notification appliances in such a way that all devices will turn on and
off at exactly the same time.
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=FUTURE USE
Programming Screen #2

Function Keys

The ES-200X keypad has 4 programmable function keys. These keys can be programmed to allow rapid disable/enable of various fire
panel inputs and outputs during scheduled maintenance. pressing any function key results in a trouble signal at the panel. Pressing 1 on
System Setup Screen #1 displays the following:
FUNCTION KEYS
1=F1
3=F3
2=F2
4=F4
Function Keys Screen
To Enable or Disable the Function Key, press the 1 key while viewing the Function Keys Screen #1. Each press of the key will toggle the
screen between Key Enabled Yes and Key Enabled No.
Pressing 2 key while viewing the Function Keys Screen #1 allows the user to select individual zones that the Function Key will control.
Pressing 3 assigns all zones to the selected Function Key.
Each function key can be assigned to control any of the 4 onboard NAC circuits on the ES-200X. By pressing the 2 key while viewing
the Function Keys Screen #2 the following screen displays, allowing the user to select the desired NAC circuit(s).
Pressing 1, 2, 3, or 4 toggles the screen between Yes (controlled by function key) and No (not controlled by function key) for each
onboard NAC circuit.
F(X) KEY OPERATION
1=NACS
2=REM SYNC DISB
Function Keys Screen #2
72
Pressing 2 for System Setup, while viewing Programming Screen #2, will cause the following screens to be
displayed:
SYSTEM SETUP
1=FUNCTION KEYS
2=BANNER
3=TIME-DATE
System Setup Screen #1
SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM
3=LANGUAGE
ENGLISH
System Setup Screen #4
1=F1
2=F2
Select 1, 2, 3, or 4 to program the corresponding Function Key. The following screens display for each
Function Key where "(X)" represents the number of the key chosen.
F(X) KEY OPERATION
1=KEY ENABLED
2=ZONES
3=ALL ZONES
Function Keys Screen #1
1=NAC 1
2=NAC 2 Y
The Remote Synchronization (TB8 on the FACP's main circuit board) can also be disabled through pro-
gramming of a function key. To disable remote synchronization, press the 3 key while viewing the Function
YES
Keys Screen #2. Each press of the key will toggle the screen between Rem Sync Disb Yes and Rem Sync
Disb No.
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
SYSTEM SETUP
1=CHARGER ENAB
24HR
2=4XTM SPV ENAB
3=REM SYNC ENAB
System Setup Screen #5
FUNCTION KEYS
3=F3
4=F4
Function Keys Screen
F(X) KEY OPERATION
NO
1=NACS
2=REM SYNC DISB
Function Keys Screen #2
F(X) NACS
Y
3=NAC 3
N
4=NAC 4
N
Function Keys Screen
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Master Programming Level
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
3=MNS OVERRIDE
System Setup Screen #3
YES
NO
YES
NO
NO