The Altronix AL1042ULADA is an extremely cost effective 10 amp remote power supply/battery charger. It may be con-
nected to any 12 or 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit
(NAC such as strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power to support
system accessories. The unit delivers electronically regulated and filtered 24 volt power to Class B, Style W, Y or Class A,
Style Z NAC loop circuits. Additionally, a separate 1 amp auxiliary output for 4-wire smoke detectors is available. The 10
amp max. alarm current can be divided between the four (4) outputs for powering NAC devices. Each output is rated at 2.5
amp max., and can be independently programmed for Steady, Temporal Code 3 or Strobe Synchronization. All outputs may
be programmed for Input to Output Follower Mode (output will follow input. i.e. March Time Input, March Time Output).
In non-alarm condition independent loop supervision for Class A, Style Z and/or Class B, Style W, Y FACP NAC circuits
is provided. In the event of a loop trouble, the FACP will be notified via the steered input (input 1 or input 2). In addition,
there are common trouble output terminals [NC, C, NO] which are used to indicate general loop/system trouble. A com-
mon trouble input is provided for optional [NC] (normally closed) devices to report trouble to the FACP. Two (2) FACP sig-
naling outputs can be employed and directed to control supervision and power delivery to any combination of the four (4)
outputs.
Agency Listings:
• UL Listed for Control Units for Fire Protective
Signaling Systems (UL 864).
• MEA - NYC Department of Buildings Approved.
• CSFM - California State Fire Marshal Approved.
• FM - Factory Mutual Approved.
• NFPA 72 Compliant.
Input:
• Power input 120VAC / 60 Hz, 5 amp.
• Two (2) Class A, Style Z or two (2) Class B,
Style W, Y FACP inputs.
• Two (2) NC dry contact trigger inputs.
Output:
• Class 2 Rated power limited outputs.
• 24VDC voltage regulated power limited outputs.
• 10 amp max total alarm current.
• 2.5A max current per output.
• Two auxiliary outputs rated at 1 amp each
(1 amp continuous, 1 amp AC disconnect).
• Programmable supervised indicating circuit outputs:
Four (4) Class B, Style W, Y or Four (4) Class A,
Style Z or Two (2) Class A, Style Z and Two (2) Class B,
Style W, Y (see Application Guide).
• Thermal and short circuit protection with auto reset.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switchover to stand-by battery when
AC fails.
• Zero voltage drop when switching over to
battery backup.
- 2 -
AL1042ULADA - NAC Power Extender
Overview:
Specifications:
Supervision:
• AC fail supervision (form "C" contact, 1 amp / 28VDC).
• Instant local AC trouble reporting relay
• Battery presence and low battery supervision
Visual Indicators:
• Input and output status LED indicators.
Special Features:
• 2-wire horn/strobe Sync mode allows audible
• Temporal Code 3, Steady Mode, Input to Output
• Compatible with 12VDC or 24VDC fire panels.
• Output loop supervision directed to input 1 or input 2.
• Signal Circuit Trouble Memory - facilitates quick
• Common trouble input and output.
• Ground fault detection.
Added Features:
• Unit includes power supply, logic board enclosure,
Enclosure Dimensions and Descriptions:
AL1042ULADA
18"H x 14.5"W x 4.625"D
Product Weight:
20 lbs.
Factory set for 30 seconds with optional 2.5 to 3 hour
delay setting (field selectable).
(form "C" contact, 1 amp / 28VDC).
(form "C" contact, 1 amp / 28VDC).
notification appliances (horns) to be silenced
while visual notification appliances (strobes)
continue to operate.
Follower Mode (maintains synchronization of
notification appliances circuit).
identification of an intermittent/fault (short circuit, open
or ground) which has previously occurred on one or
more signaling circuit outputs. LEDs indicate/identify
which output the fault has occurred.
cam lock, and battery leads.
AL1042ULADA
Need help?
Do you have a question about the AL1042ULADA and is the answer not in the manual?
Questions and answers