The web server's write access ability can be disabled for security purposes by setting P492 to "1".
TIP!
To ensure that the drive is network control ready, open the Get/Set Parameter. Write a value of 97 to register 65 to
start the drive. Write a value to P61 (ex 212 = 21.2Hz).Then write a value of 0 to 65 to stop the drive.
WARNING!
Make sure it is safe to operate the driven equipment prior to starting the SMV drive from the network. Damage to
equipment and/or injury to personnel can result.
CMVETH01B
Commissioning
SMVector Programming & Configuration
Basic Setup
No.
P100
Start Control Source
P112
Rotation
P121
TB-13A Input Function
P122
TB-13B Input Function
P123
TB-13C Input Function
Figure 12: SMV Commissioning - Basic Setup
SMVector Programming & Configuration
Get/Set Parameter
Parameter Number
Parameter Value
Read
Figure 13: SMV Commissioning - Get/Set Parameter
Name
0 - Local Keypad
1 - Forward and Reverse
9 - Network Enable
10 - Reverse Rotation
8 - Control Select
Read
16
Selection / Setting
Write
0
0
Write