Section 3-3-1: Venting Layout: Wall Mounted Termination; Top Venting Graph - Montigo H34DF Installation & Maintenance Manual

H34 series indoor gas fireplace
Table of Contents

Advertisement

Section 3-3-1: Venting Layout: Wall Mounted Termination

Top Venting Graph

Measure the vertical height from the fireplace hearth to the centre of
the termination and the horizontal run from the fireplace flue collar to
the wall flange of the termination. Plot on the Venting Graph with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Selection of components and details of venting layout should adhere
to the following guidelines:
• Vent terminations must not be recessed in walls or siding.
• For Heat Shield requirements see Section 3-3.
• Once the proposed venting layout has been determined refer to
graph to ensure the layout is acceptable.
Notes Wall Mounted Terminations: TOP VENT
• All measurements for vertical or horizontal runs are measured from
center of the vent pipe.
• Venting runs must fall within the limits set by the venting graph.
Wall mounted Terminations:
The following details are some possible configurations for Wall mounted
terminations. See below.
40" Max. for minimum vertical
Flex section
Flex section
Hearth
Hearth
Figure 8. Top Vented, wall mounted installation with 1 elbow (1 one 90° bend). The vent run
must comply with Venting Graph for Top vent, wall mounted terminations
14
44" Max. (NG)
16" Max. (LP)
Heat
Heat Shield
Shield
Termination
Termination
39" Min. (NG)
39" Min. (NG)
63" Min. (LP)
Exterior
Exterior
Wall
Wall
H34DFN (TRADITIONAL) VENT RUN
132
120
Acceptable vent run
within non-shaded area.
108
96
84
72
60
48
36
24
12
0
0
12
24
36
48
60
Horizontal Run (In.)
Figure 8.b H34DFN Top Vent Venting Graph for wall mounted terminations
HLB34DF*, HLB34DF*-2 VENT RUN
132
120
Acceptable vent run
within non-shaded area.
108
96
84
72
60
48
39''
36
24
40''
12
0
0
12
24
36
48
60
Horizontal Run (In.)
Figure 8.c H*34DF* Top Vent Venting Graph for wall mounted terminations
15'Max.
for minimum
30"min
30" Min.
Flex Section
Flex section
Hearth
Hearth
Figure 8.d Top Vented, wall mounted Multi-elbow installation. The vent run must comply with
Venting Graph for Top vent, wall mounted terminations,
Installation
39''
Unacceptable vent run
72''
within shaded area.
72
84
96
108
120
132
144
156
168 180
Unacceptable vent run
within shaded area.
72
84
96
108
120
132
144
156
168 180
15' Max.
Heat
vertical
Heat
Shield
Shield
Termination
Termination
Solid section
9' Min at Max.
Horizontal(NG)
8' Min at Max.
10' Min at Max.
Horizontal(LP)
Exterior
Exterior
Wall
Wall
XG0146 - 180405
Horizontal