Section 3-3-1: Venting Layout: Wall Mounted Termination - Montigo PL38DF Installation & Maintenance Manual

Pl series
Table of Contents

Advertisement

PL38DF* Indoor Gas Fireplace
Section 3-3-1: Venting Layout: Wall Mounted
Termination
Selection of components and details of venting layout should adhere
to the following guidelines:
Vent terminations must not be recessed in walls or siding.
For Heat Shield requirements see Section 3-3-3 on page 18.
Once the proposed venting layout has been determined
refer to Figure 12, 12a, 15, or 15a to ensure the layout is
acceptable.
Notes Wall Mounted Terminations: TOP VENT
All measurements for vertical or horizontal runs are measured
from center of the vent pipe.
Venting runs must fall within the limits set by the venting
graph, see Figure 12 or 12a.
Wall mounted Terminations
The following details are some possible configurations for Wall
mounted terminations. See below.
The Venting Graph:
Measure the vertical height from the fireplace hearth to the centre
of the termination and the horizontal run from the fireplace flue
collar to the wall flange of the termination. Plot on the Venting
Graph Figure 12 or 12a with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 120" and the
horizontal run to the wall flange of the vent termination is
144", this would be an acceptable installation.
Example B: (Unacceptable Installation)
If the vertical dimension from the hearth is 36" and the horizontal
run to the wall flange of the vent termination is 84", this would
not be an acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 60"
and the horizontal run to the wall flange of the vent termination
is 144", this would not be an acceptable installation.
Acceptable vent run
within non-shaded area.
B
63"
16 "
Figure 12. PL38DF* LP Top Vent Venting Graph for wall mounted
terminations.
Page 14
Installation
A
C
Unacceptable vent run
within shaded area.
If your installation does not fall
within the venting parameters,
please contact a local Montigo
dealer for Power Venting options.
Acceptable vent run
within non-shaded area.
B
39"
44 "
Figure 12a. PL38DF* NG Top Vent Venting Graph for wall mounted
terminations.
Flex section
Hearth
Top Vented, wall mounted installation with one 90°
Figure 13.
bend. The vent run must comply with Venting Graph for Top
vent, wall mounted terminations, Figure 12 or 12a.
15'Max.
30"min
Flex Section
Hearth
Top Vented, wall mounted Multi-elbow installation. See
Figure 13a.
Venting Graph for Top vent, wall mounted terminations, Figure 12
or 12a.
A
C
Unacceptable vent run
within shaded area.
If your installation does not fall
within the venting parameters,
please contact a local Montigo
dealer for Power Venting options.
44" Max. (NG)
16" Max. (LP)
Heat
Shield
Termination
39" Min. (NG)
63" Min. (LP)
Exterior
Wall
Heat
Shield
Termination
Solid Section
8' MIN AT MAX
Horizontal
Exterior
Wall
XG0216 - 160215.1