Summary of Contents for Rockwell Automation PowerFlex 40
Page 1
PowerFlex 40 Configured AC Drives INSTALLATION INSTRUCTIONS...
Page 2
Burn Hazard labels may be located on or inside the equipment (e.g., drive or motor) to alert people that surfaces may be at dangerous temperatures. PowerFlex, DriveExplorer, DriveExecutive, DPI, and SCANport are either trademarks or registered trademarks of Rockwell Automation, Inc.
Installation Instructions is designed to provide only basic installation and operation information. For this reason, the following topics have not been included: • Troubleshooting • Start-Up • Programming and Parameters Please refer to the PowerFlex 40 User Manual for detailed drive information. Publication 23B-IN001G...
Control A Global Reference Guide for Reading 0100-2.10 Schematic Diagrams Guarding Against Electrostatic Damage 8000-4.5.2 For detailed PowerFlex 40 information including drive parameters, programming, start-up, troubleshooting, specifications: Title Publication Available Online at … PowerFlex 40 User Manual 22B-UM001… www.rockwellautomation.com/literature PowerFlex Reference Manual PFLEX-RM001…...
ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged before performing any work on the drive. Measure the voltage at the drive (Refer to the PowerFlex 40 User Manual for test point locations). The voltage must be zero. Compliance Certification Certifications are applicable to approved program defined options.
Overview Catalog Number The PowerFlex 40 Adjustable Frequency AC Standard Configured Drives catalog numbering scheme is shown below. Explanation Position – – Drive Options Code Type Code Interface Module Code Description PowerFlex 40 Fixed Keypad on Drive DeviceNet Quick Disconnect...
Chapter PowerFlex 40 Standard Configured Drive Standard Features and Options Chapter Objectives This chapter describes the standard features and operation for PowerFlex 40 Standard Configured Drives and associated options. For information on … See page … Standard Features Enclosure Options...
PowerFlex 40 Standard Configured Drive Standard Features and Options Enclosure Options NEMA/UL Type 4 (Position 9, Code D) The enclosure provided is a NEMA/UL Type 4, painted mild steel, which supports both NEMA/UL Type 4 and NEMA/UL Type 12 applications.
PowerFlex 40 Standard Configured Drive Standard Features and Options Communication Options DeviceNet (Position 12, Code D) The DeviceNet option is drive mounted and consists of the DeviceNet communication adaptor (22-COMM-D) and adaptor cover (22B-CCB for frame B drives or 22B-CCC for frame C drives). When DeviceNet is present, no other communication option is available other than the HIM.
PowerFlex 40 Standard Configured Drive Standard Features and Options Power Disconnect Options Drive Motor Circuit Protector (Position 16+, Code -P3) The Drive Motor Circuit Protector option is factory installed and provides a manual means of disconnecting input power to the drive. The Allen-Bradley Bulletin 140M switch is designed to meet short circuit requirements for branch circuit protection.
Page 13
PowerFlex 40 Standard Configured Drive Standard Features and Options Drive Input Fused Disconnect Switch (Position 16+, Code -P6) The Drive Input Fused Disconnect Switch option is factory installed and provides a manual means of disconnecting input power to the drive. The Allen-Bradley Bulletin 194R switch is designed to meet disconnect switch requirements for branch circuit protection.
Page 14
Table are applicable for one drive per branch circuit. No other load may be applied to that fused circuit. The recommended fuse type for all PowerFlex 40 Standard Configured Drives is UL Class J. Table 1.A Branch Fusing Voltage Rating...
Page 15
PowerFlex 40 Standard Configured Drive Standard Features and Options Input Power Wiring Refer to the PowerFlex 40 User Manual for additional detailed information about input power wiring recommendations and selection. ATTENTION: Protect the contents of the options cabinet from metal chips and other debris while drilling the conduit openings.
Page 16
PowerFlex 40 Standard Configured Drive Standard Features and Options Output Power Wiring Refer to the PowerFlex 40 User Manual for additional detailed information about output power wiring recommendations and selection. ATTENTION: Unused wires in conduit must be grounded at both ends to avoid a possible shock hazard caused by induced voltages.
PowerFlex 40 Standard Configured Drive Standard Features and Options Operator Device Options Hand/Off/Auto Selector Switch (Position 16+, Code S1) This 800F door mounted operator device is factory installed and provides a Hand/Off/Auto selector switch. The Hand/Off/Auto selector switch will start the drive in Hand mode and stop the drive in Off mode.
Page 18
1-10 PowerFlex 40 Standard Configured Drive Standard Features and Options Auto/Manual Selector Switch (Position 16+, Code S4) This 800F door mounted operator device is factory installed and provides an Auto/Manual selector switch. The Auto/Manual selector switch determines the source of the actual drive speed reference.
Page 19
PowerFlex 40 Standard Configured Drive Standard Features and Options 1-11 Start and Stop Push Buttons (Position 16+, Code S7) This option provides factory installed 800F Start and Stop push buttons. In all cases, the Stop input to the drive must be present before the drive will start.
Page 20
1-12 PowerFlex 40 Standard Configured Drive Standard Features and Options Local Speed Potentiometer (Code S18) This option provides a factory installed 800F door mounted one turn potentiometer for speed control. The device provides the speed source when no digital inputs are active.
Page 21
PowerFlex 40 Standard Configured Drive Standard Features and Options 1-13 Local/Off/Remote Selector Switch With One Normally Open Interposing Relay (Code S21) This 800F door mounted operator device and interposing relay option is factory installed and provides a Local/Off/Remote selector switch.
Page 22
1-14 PowerFlex 40 Standard Configured Drive Standard Features and Options Spring Return Hand-Off-Auto Selector Switch (Code S22) This 800F door mounted operator device is factory installed and provides a Hand/Off/Auto selector switch. The Hand position is equipped with a spring return.
1-16 PowerFlex 40 Standard Configured Drive Standard Features and Options I/O Options DeviceNet I/O (4 In/2 Out) w/Spring Return HOA and Power Disconnect Aux. Contact (Position 16+, Code R3) This option provides a factory installed 800F door mounted operator device, a 100-DNY42R and a power disconnect auxiliary contact mounted internal to the cabinet.
Page 25
PowerFlex 40 Standard Configured Drive Standard Features and Options 1-17 DeviceNet Point I/O w/IB4 (4 Inputs) (Position 16+, Code R4) This option provides a factory installed 1734-ADNX Point I/O Scanner in combination with a 1734-IB4 (4 input) four point, 24V DC sink input.
Page 26
1-18 PowerFlex 40 Standard Configured Drive Standard Features and Options DeviceNet I/O (4 In/ 2 Out) w/Spring Return HOA, Power Disconnect Aux. Contact, and 4 I/O Quick Disconnects (Position 16+, Code R5) This option provides a factory installed 800F door mounted operator device,...
Control Wiring Overview Schematic Drawings Control Wiring Overview Refer to the PowerFlex 40 User Manual for additional detailed information about control and signal wiring. The Control I/O Terminal Block (TB1) and Relay Terminal Block (TB2) located on the drive Main Control Board provide terminals for interfacing customer supplied control inputs and outputs.
Maximum Surrounding Air Temperature PowerFlex 40 Standard Configured Drives are designed to operate at -10° to 40°C (14° to 104°F) surrounding air temperature. The design of the PowerFlex Standard Configured Drive supports indoor and outdoor applications that are not in direct sunlight.
Mechanical Installation Figure 3.1 Minimum Mounting Clearances Dimensions are in millimeters and (inches). 152.4 (6.00) Drive or other device 152.4 152.4 (6.00) (6.00) 152.4 (6.00) Dimensions Figure 3.2 Frame B Dimensions Dimensions are in millimeters and (inches). 405.9 (15.98) 393.2 (15.48) 355.6 287.5...
Page 51
Mechanical Installation Figure 3.3 Frame C Dimensions Dimensions are in millimeters and (inches). Frame C P3 Option 383.3 (15.09) P6 Option 364.2 16.0 457.2 (14.34) (0.63) (18.00) 425.2 177.8 146.1 (16.74) (7.00) (5.75) 460.8 (18.14) 427.2 (16.82) 406.4 (16.00) Detail 19.1 (0.38) (0.75)
Carrier Frequency: 2-4 kHz. Drive rating and heat calculations are based on 4 kHz. (1) The design of the PowerFlex 40 Standard Configured Drive NEMA 4/12 and 4X packages support indoor and outdoor applications that are not in direct sunlight.
Page 60
Replacement Parts Table B.F Miscellaneous Description Designation Voltage Part Number Manufacturer 0.5-5.0 2410ML-05W-B30-B00 NMB Tech Publication 23B-IN001G...