8.4.16 STD Compressor Motor Overcurrent/Lock

E0
Error Code
Applicable
LRYEQ16AY1
Models
Method of Error
Detects the overcurrent with current sensor (CT).
Detection
Error Decision
Error is decided when the detected current value exceeds 15.0A for 2 seconds.
Conditions
Supposed
Causes
187
Stop valve is not opened
Obstacles at the air outlet
Improper power voltage
Defective magnetic switch
Defective compressor
Defective current sensor (A7P, A8P)