3. Standard Specification

3.1
Standard Specification

3.1.1 Outdoor Unit

Model
Power Supply
Outdoor operating
temperature range
Cooling
1
Capacity
(kW)
Heating
Casing Color
Dimensions: (H×W×D)
Heat Exchanger
Type
Piston Displacement
Compressor
Number of Revolutions
Motor Output × Number of Units
Starting Method
Type
Motor Output
Fan
Airflow Rate
Drive
Liquid pipe
Connecting
Pipes
Gas pipe
Receiver Volume
Mass
Safety Devices
Refrigerant Name
Refrigerant
Charge Volume
Control
Refrigerant Oil Name
Refrigerant
Oil
Charge Volume
Operating Sound
Standard Accessories
Note
1 Operating conditions of outdoor unit
(Air conditioning side)
Indoor temperature: 27°CDB/19°CWB, Outdoor temperature: 32°CDB, Piping length: 7.5m, Level difference: 0m (In cooling priority mode)
(Refrigeration side)
Evaporating temperature: -10°C, Outdoor temperature: 32°CDB, Suction SH: 10°C (In cooling priority mode)
(Heating conditions)
Indoor temperature: 20°CDB, Outdoor temperature: 7°CDB/6°CWB, Refrigeration load: 18kW, Piping length: 7.5m, Level difference: 0m
Saturated temperature equivalent to suction pressure (Refrigeration side): -10°C (Under chilled condition), Connection capacity for indoor air-conditioner: 10HP, When
heat recovery is 100%
CONVENI-PACK
Cooling
Heating
Air conditioning
Refrigeration
Air conditioning
Refrigeration
mm
3
m
/h
r.p.m
kW
kW
3
m
/min
50m
or
Air
less
conditioning
50 ~
130m
50m
or
less
Refrigeration
50 ~
130m
50m
or
Air
less
conditioning
50 ~
130m
50m
or
less
Refrigeration
50 ~
130m
kg
kg
L
dB(A)
Installation Manual, Operation Manual, Connection Pipes, Clamping Materials,
LRYEQ16AY1
[LRYEQ16AY1E]
3 phase 50Hz 380-415V
-5°C~43°CDB
-15°C~15.5°CWB, -15°C~21°CDB
14.0 (In cooling priority mode)
21.8 (In cooling priority mode)
27.0 (In heat recovery 100% mode)
21.8 (In heat recovery 100% mode)
Ivory white (5Y7.5/1) [Light camel (2.5Y6.5/1.5)]
1680×1240×765
Hermetically sealed scroll type
13.34+10.53+10.53
6300, 2900, 2900
(2.5+3.6+4.5)×1
Direct-on-line (Inverter system)
φ9.5 C1220T (Brazing connection)
φ12.7 C1220T (Brazing connection)
φ9.5 C1220T (Brazing connection)
φ12.7 C1220T (Brazing connection)
φ25.4 C1220T (Brazing connection)
φ28.6 C1220T (Brazing connection)
φ25.4 C1220T (Brazing connection)
φ28.6 C1220T (Brazing connection)
High Pressure Switch, Fan Driver Overload Protector, Overcurrent Relay,
Inverter Overload Protector, Fusible Plug, Earth Leakage Detector
Electronic Expansion Valve
DAPHNE FVC68D
1.7+2.1+2.1+4.0
Declaration of Conformity, Refr. Label for F-gas Regulation
Standard Specification
Cross fin coil
Propeller fan
0.75×2
230
Direct drive
13.5
370
R-410A
11.5
62
14