8.4.51 Transmission Error between Indoor Units and Outdoor Units

U4
Error Code
Applicable
All indoor models
LRYEQ16AY1
Models
Method of Error
Check if the transmission between indoor unit and outdoor unit is correctly executed using
micro-computer.
Detection
Error Decision
When transmission is not carried out normally for a certain amount of time
Conditions
Supposed
Causes
239
Indoor to outdoor, outdoor to outdoor transmission wiring F1, F2 disconnection, short circuit
or wrong wiring
Outdoor unit power supply is OFF
System address does not match
Defective outdoor unit PCB (A1P)
Defective indoor unit PCB