Momentary Overcurrent Of Inverter Compressor - Daikin LRYEQ16AY1 Service Manual

Conveni-pack
Table of Contents

Advertisement

SiBE811001EB

8.4.43 Momentary Overcurrent of Inverter Compressor

L8
Error Code
Applicable
LRYEQ16AY1
Models
Method of Error
Error is detected from the current flowing in the power transistor.
Detection
Error Decision
When inverter secondary current is below.
(1) 19.0A or more continues for 5 seconds.
Conditions
(2) 16.1A or more continues for 260 seconds.
Supposed
Causes
CONVENI-PACK
Compressor overload
Compressor coil disconnected
Defective inverter PCB
Disconnection wire of compressor
Troubleshooting
226