Troubleshooting
8.4.23 Electronic Expansion Valve Coil Abnormality
E9
Error Code
Applicable
LRYEQ16AY1
Models
Method of Error
Check disconnection of connector
To be detected based on continuity existence of electronic expansion valve coil
Detection
Error Decision
No current is detected in the common (COM [+]) when power supply is ON.
Conditions
Supposed
Causes
201
Disconnection of connectors for electronic expansion valve (Y1E~Y5E)
Defective electronic expansion valve coil
Defective outdoor unit main PCB or sub PCB
SiBE811001EB