Powerwall Dimensions And Space Requirements; Powerwall Temperature Requirements - Tesla Powerwall 2 AC Installation Manual

Backup gateway
Hide thumbs Also See for Powerwall 2 AC:
Table of Contents

Advertisement

Powerwall Dimensions and Space Requirements

Figure 2: Powerwall 2 Dimensions and Space Requirements
Minimum lateral wall space
Minimum clearance from left side (air intake)
Minimum clearance from right side (air exhaust)
Minimum clearance above single Powerwall
Minimum clearance above side-by-side Powerwalls
Minimum clearance between side-by-side Powerwalls
Maximum height above ground
Maximum slope

Powerwall Temperature Requirements

Powerwall is capable of charging and discharging within the full ambient temperature range
listed in the Specifications section. At the high and low ends of the temperature range,
Powerwall may limit charge or discharge power based on battery cell temperature to improve
battery lifespan.
Installation in full sun raises the temperature inside the enclosure above ambient temperature.
This temperature rise is not a safety risk, but may impact battery performance. To optimize
performance, avoid installing Powerwall in locations that are exposed to the sun for extended
periods.
Do not install Powerwall in locations with sustained high or low temperatures. The average
ambient temperature over the system's life should be between 0°C and 30°C (32°F and 86°F).
8
Powerwall Space Requirements
960 mm (38 in)
50 mm (2 in)
150 mm (6 in)
50 mm (2 in)
300 mm (12 in)
250 mm (10 in)
1 m (3.3 ft) to bottom of unit
+/ – 2° side-to-side
+/– 5° front-to-back
Powerwall Installation Manual