Powerwall Inverter Adjustable Settings - Tesla Powerwall 2 AC Installation Manual

Backup gateway
Hide thumbs Also See for Powerwall 2 AC:
Table of Contents

Advertisement

The Powerwall inverter has the following adjustable settings, which are determined when the
system is commissioned.
NOTE: Under abnormal voltage or frequency conditions or in response to a detected
unintentional island, the system will disconnect from the grid by opening its internal contactor.
NOTE: All values are for factory default 240 V @ 60 Hz.
Voltage Ride-Through
The Powerwall inverter has three voltage and time set points for low voltage ride-through,
configurable to the following ranges (measured as line to neutral for single-phase, and line-to-
line for split-phase):
Parameter
LVRT Point 3
0-400 V
LVRT Point 2
0-400 V
LVRT Point 1
0-400 V
LVRT Point 0
0-400 V
*Voltage accuracy 2% of nominal
The inverter has three voltage and time set points for high voltage ride-through, configurable
to the following ranges (measured as line to neutral for single-phase, and line to line for split-
phase):
Voltage
Parameter
HVRT Point 3
0-400 V
HVRT Point 2
0-400 V
HVRT Point 1
0-400 V
HVRT Point 0
0-400 V
*Voltage accuracy 2% of nominal
The above tables represent the maximum parameter values that the user can input. However,
240 VAC nominal systems are limited to a maximum HVRT of 120%.
The inverter ships with the pre-defined settings listed below.
Interconnection System Default Response to Abnormal Voltages
Voltage Range (% of base voltage)
42

Powerwall Inverter Adjustable Settings

Inverter LVRT Settings
Voltage
Default Value*
Range*
108 V
144 V
192 V
216 V
Inverter HVRT Settings
Default Value*
Range*
336 V
288 V
264 V
254.4 V
V < 45
45 ≤ V < 60
60 ≤ V < 88
110 < V < 120
V ≥ 120
Time
(sec)
0-60
100 ms or 1%, whichever is greater
0-60
100 ms or 1%, whichever is greater
0-60
100 ms or 1%, whichever is greater
0-60
100 ms or 1%, whichever is greater
Time
(sec)
0-60
100 ms or 1%, whichever is greater
0-60
100 ms or 1%, whichever is greater
0-60
100 ms or 1%, whichever is greater
0-60
100 ms or 1%, whichever is greater
Clearing Time (s)
0.16
1
2
1
0.16
Powerwall Installation Manual